clint EURICE.png

clint tec_ec_inverter_fans.png

EHW/EC 29÷73

WALL MOUNTED FAN COIL UNITS WITH EC INVERTER TANGENTIAL FAN

SOLO_FREDDO.png caldo_e_freddo1.png icon_EC_tangential_fans_14.png H2O.png

These hydronic Fan Coil units are designed for wall-mounted installation in domestic environments or service sector including offices and shops.
Part of an hydronic system equipped with a liquid Chiller, the wall-mounted Fan Coil unit generates cool air silently and with instantaneous reaction. During the winter, if combined with a boiler or heat pump, it provides warm air, making it possible to meet home or business heating needs.
A filter, which absorbs and retains dust in suspension, allows to keep the air quality at a suitable level and its easy removal enables continuous cleaning cycles to be carried out which are particularly important in order to guarantee suitable hygiene standards in highly frequented rooms.
It is provided with remote control, 3-Way valve, flexible hydraulic hook-ups for easy installation and maintenance operations, and is also pre-set for master-slave functioning, with RS485 serial interface. The units are equipped with EC Inverter motor that can modulate the air flow ensuring a perfect adaptability to the load without any temperature fluctuations achieving superior performance compared to the traditional solutions even from energy consumption point of view.

Versions

  • EHW/EC - Base unit with 3-Way valve and remote control

Power range

  • 2.1-5.4 kW
  • 0.6-1.5 Ton

Features

  • High design appearance with rounded lines, structure in ABS with improved mechanical features resistant to aging.
  • Heat exchanger coils with copper pipes and aluminium fins with elevated heat exchanging surfaces; equipped with air blowing in condensation drain.
  • 3-Way water valve incorporated inside the unit.
  • Tangential fan unit with EC INVERTER motor, maximum silent operations, air flow fins with adjustable horizontal direction and motorized deflector fin controllable via remote control.
  • Microprocessor control with timer for on/off programming. Program for automatic operations, cooling, heating and ventilation; night wellness program and dehumidifier.
  • Automatic restarting after power outage
  • Flexible water connections for easy installation and maintenance operations.
  • Easy removal and cleaning of air filter, maintaining appropriate air quality.
  • Infrared remote control with wall support.

Loose accessories

  • EH Supplementary electrical heater
  • DRC Wall mounted automatic electronic control panel
293338465873
CoolingTotal cooling capacity (1)kW2,072,493,023,744,815,38
Sensible cooling capacity (1)kW1,521,812,222,743,463,89
Water flow (1)l/h355427525642826924
Pressure dropskPa222839384552
HeatingHeating capacity (2)kW2,703,213,934,876,106,85
Water flow (2)l/h355427525642826924
Pressure dropskPa182332293443
Water connectionsIn / Out"G½"½"½"½"½"½"
Air flowMaxm³/h5005006457889801240
Medm³/h370370445740760760
Minm³/h290290370570600600
Electrical characteristicsPower supplyV/Ph/Hz230/1/50230/1/50230/1/50230/1/50230/1/50230/1/50
Max absorbed powerkW0,0140,0140,0200,0300,0420,060
Sound pressureMax (3)dB(A)373743464045
Med (3)dB(A)303034403535
Min (3)dB(A)262629343030
WeightsTransport weightkg141515161818
Operating weightkg121313141616

Dimensions

293338465873
LSTDmm87587587587510601060
WSTDmm220220220220240240
HSTDmm300300300300310310

Notes

  • 1 Ambient air temperature 27 °C d.b./19 °C w.b., water temperature 7/12 °C.
  • 2 Ambient air temperature 20 °C d.b., water temperature 50 °C.
  • 3 Sound pressure level measured at 1 m from the unit with reverberation time 0,5 s.
  • N.B. (1) Maximum operating pressure 1000 kPa.
  • N.B. (2) Maximum inlet water temperature 70 °C.
  • N.B. (3) Inhibited ethylene glycol can be added to the water.