JWA/FC 051÷172 S/K/P
Aircooled liquid chillers free-cooling with axial fans, scroll compressors and plate exchanger
The liquid Chillers of the JWA/FC 051÷172 S/K/P series, with R410A refrigerant, offer innovative technology for both domestic as well as industrial applications requiring the production of cooled water continuously year-round.
During the cold months, in the FREE-COOLING operation mode, the return liquid of the system is cooled directly by forced convection of outdoor air through the condensing coil, thus saving energy by not operating the unit's Scroll compressors. A 3-way valve system is controlled by the electronic microprocessor controller, allowing functioning in CHILLER, FREE-COOLING or MIXED (simultaneously CHILLER and FREE-COOLING) modes.
Are available as option the new EC Inverter fans with high available static pressure and efficiency for ducted installation.
The units are compliant to the 2021 ErP Regulation for process cooling application.
On request, units can be supplied with R452B or R454B refrigerant.
Versions
- JWA/FC - Cooling only
Power range
- 53.0-174 kW
- 15.0-50.0 Ton
Features
- Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
- Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
- Axial fans directly coupled to an electric motor with external rotor.
- Condenser made of copper tubes and aluminium finned coil combined with FREE-COOLING coil.
- Evaporator AISI 316 stainless steel braze welded plates type with one circuit on the refrigerant side and one on the water side in 051÷131 models; with two independent circuits on the refrigerant side and one on the water side in 152÷172 models, complete with water differential pressure switch.
- Electronic high and low pressure gauges.
- R410A refrigerant. On request R452B or R454B refrigerant.
- Electrical board includes: main switch with door safety interlock, fuses, thermal protection relays for compressors and thermocontacts for fans.
- Condensing Control is included: electronic proportional device that ensures efficient and continuous functioning of the unit with outside air temperature down to –20 °C. It also allows to reduce the sound level especially at night. It consists of a fans speed controller with continuous speed regulation, high and low pressure transducers on cooling circuit and an electrical heater on electrical board.
- Microprocessor control and regulation system.
Accessories
Factory fitted accessories
- IM Automatic circuit breakers
- SL Unit silencement
- RFM Cooling circuit shut-off valve on discharge line
- RFL Cooling circuit shut-off valve on liquid line
- BT Low water temperature kit
- EC EC Inverter fans
- ECH EC Inverter fans with high available static pressure
- TX Coil with pre-coated fins
- SI Inertial tank
- PS Single circulating pump
- PD Double circulating pump
- GS Single circulating pump gasket for glycol >30%
- GD Double circulating pump gaskets for glycol >30%
- SS Soft start
- IS Modbus RTU protocol, RS485 serial interface
- IST Modbus TCP/IP protocol, Ethernet port
- ISB BACnet MSTP protocol, RS485 serial interface
- ISBT BACnet IP protocol, Ethernet port
- ISS SNMP protocol, Ethernet port
- MN High and low pressure gauges
Loose accessories
- CR Remote control panel
- RP Coils protection metallic guards
- AG Rubber shock absorbers
- AM Spring shock absorbers
Technical data
051 | 061 | 071 | 081 | 091 | 101 | 111 | 131 | 152 | 172 | |||
Cooling | Cooling capacity (1) | kW | 52,7 | 59,5 | 68,1 | 76,7 | 85,7 | 99,1 | 114 | 130 | 151 | 174 |
Absorbed power (1) | kW | 18,1 | 20,3 | 23,3 | 26,1 | 29,3 | 36,8 | 42,2 | 48,4 | 54,4 | 64,9 | |
EER (1) | 2,91 | 2,93 | 2,92 | 2,94 | 2,92 | 2,69 | 2,70 | 2,69 | 2,78 | 2,68 | ||
Cooling (EN14511) | Cooling capacity (1) | kW | 52,0 | 58,8 | 67,3 | 75,9 | 84,9 | 98,2 | 113 | 129 | 150 | 172 |
Absorbed power (1) | kW | 18,8 | 21,0 | 24,1 | 26,9 | 30,1 | 37,7 | 43,5 | 49,9 | 55,7 | 66,4 | |
EER (1) | 2,77 | 2,80 | 2,79 | 2,82 | 2,82 | 2,60 | 2,60 | 2,59 | 2,69 | 2,59 | ||
SEPR (2) | 5,11 | 5,13 | 5,12 | 5,14 | 5,12 | 5,11 | 5,09 | 5,08 | 5,15 | 5,14 | ||
Free-Cooling cycle | Air temperature (3) | °C | 2,1 | 1,3 | 0,0 | -2,4 | -3,5 | 1,0 | 0,0 | -1,1 | -3,0 | -4,8 |
Absorbed power (3) | kW | 2 | 2 | 2 | 2 | 2 | 6 | 6 | 6 | 8 | 8 | |
Compressor | Quantity | n° | 2 | 2 | 2 | 2 | 2 | 3 | 3 | 3 | 4 | 4 |
Refrigerant circuits | n° | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 2 | 2 | |
Capacity steps | n° | 2 | 2 | 2 | 2 | 2 | 3 | 3 | 3 | 4 | 4 | |
Water circuit. | Water flow | l/s | 2,72 | 3,07 | 3,52 | 3,96 | 4,43 | 5,09 | 5,88 | 6,70 | 7,78 | 8,93 |
Pressure drops | kPa | 115 | 105 | 120 | 100 | 100 | 100 | 135 | 145 | 102 | 106 | |
Water connections | "G | 2" | 2" | 2" | 2" | 2" | 2 ½" | 2 ½" | 2 ½" | 2 ½" | 2 ½" | |
Electrical characteristics | Power supply | V/Ph/Hz | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 |
Max. running current | A | 35 | 41 | 48 | 54 | 65 | 76 | 85 | 102 | 113 | 136 | |
Max. starting current | A | 130 | 140 | 144 | 169 | 209 | 173 | 201 | 246 | 229 | 280 | |
Unit with tank and pump | Pump available static pressure | kPa | 120 | 125 | 100 | 115 | 100 | 190 | 145 | 125 | 150 | 125 |
Tank water volume | l | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 600 | 600 | |
Water connections | "G | 2 ½" | 2 ½" | 2 ½" | 2 ½" | 2 ½" | 2 ½" | 2 ½" | 2 ½" | 2 ½" | 2 ½" | |
ECH fan available static pressure | Pa | 110 | 110 | 110 | 105 | 105 | 60 | 60 | 60 | 65 | 65 | |
Sound pressure | STD version (4) | dB(A) | 63 | 63 | 63 | 63 | 64 | 65 | 66 | 66 | 67 | 67 |
With SL accessory (4) | dB(A) | 61 | 61 | 60 | 60 | 62 | 63 | 64 | 64 | 65 | 65 | |
Weights | Transport weight (5) | kg | 923 | 932 | 951 | 980 | 999 | 1308 | 1317 | 1350 | 1472 | 1510 |
Operating weight (5) | kg | 970 | 980 | 1000 | 1030 | 1050 | 1390 | 1400 | 1435 | 1560 | 1600 |
Dimensions
051 | 061 | 071 | 081 | 091 | 101 | 111 | 131 | 152 | 172 | |||
L | STD | mm | 3550 | 3550 | 3550 | 3550 | 3550 | 4700 | 4700 | 4700 | 4700 | 4700 |
W | STD | mm | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 |
H | STD | mm | 2220 | 2220 | 2220 | 2220 | 2220 | 2235 | 2235 | 2235 | 2235 | 2235 |
Notes
- 1 Chilled water (with ethylene glycol at 30%) from 15 to 10 °C, ambient air temperature 35 °C.
- 2 Seasonal energy efficiency of high temperature process cooling according to EU Regulation No. 2016/2281.
- 3 Ambient air temperature at which the cooling capacity indicated in point (1) is reached.
- 4 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
- 5 Unit without tank and pump.
Documents
- Product overview (EN) _ktk_dpl_over_2022_ENG_w.pdf
- Product guides (EN) KTK_Product_Guide_ENG_05_2022.pdf
- Commercial leaflets (EN) _ktk_dpl_low_gwp_refrigerants_technical_handbook_ENG_07.2022.pdf
- Commercial leaflets (EN) _ktk_dpl_low_gwp_refrigerants_commercial_ENG_07.2022.pdf
- Technical brochures 09_jwa-fc_051-172_s-k-p_ktb_38.7.pdf
- Installation, use and maintenance manuals (IT) IT_JWA_FC_051_172_S_K_P__KTM-38.7_REV8.pdf
- Installation, use and maintenance manuals (IT) IT_JWA_FC_051_172_S_G_P__KTM-38.9_REV6.pdf
- Installation, use and maintenance manuals (IT) IT_JWA_FC_051_172_S_L_P__KTM-38.9_REV6.pdf
- Installation, use and maintenance manuals (EN) EN_JWA_FC_051_172_S_K_P__KTM-38.7_REV8.pdf
- Installation, use and maintenance manuals (EN) EN_JWA_FC_051_172_S_G_P__KTM-38.9_REV6.pdf
- Installation, use and maintenance manuals (EN) EN_JWA_FC_051_172_S_L_P__KTM-38.9_REV6.pdf
- Installation, use and maintenance manuals (DE) DE_JWA_FC_051_172_S_K_P__KTM-38.7_REV8.pdf
- Installation, use and maintenance manuals (DE) DE_JWA_FC_051_172_S_G_P__KTM-38.9_REV6.pdf
- Installation, use and maintenance manuals (DE) DE_JWA_FC_051_172_S_L_P__KTM-38.9_REV6.pdf
- Installation, use and maintenance manuals (FR) FR_JWA_FC_051_172_S_K_P__KTM-38.7_REV8.pdf
- Installation, use and maintenance manuals (FR) FR_JWA_FC_051_172_S_G_P__KTM-38.9_REV6.pdf
- Installation, use and maintenance manuals (FR) FR_JWA_FC_051_172_S_L_P__KTM-38.9_REV6.pdf
- Installation, use and maintenance manuals (ES) ES_JWA_FC_051_172_S_K_P__KTM-38.7_REV8.pdf
- Installation, use and maintenance manuals (ES) ES_JWA_FC_051_172_S_G_P__KTM-38.9_REV6.pdf
- Installation, use and maintenance manuals (ES) ES_JWA_FC_051_172_S_L_P__KTM-38.9_REV6.pdf