TWH/DR 341÷2061 TT/H

A CLASS energy efficiency watercooled liquid chillers with TURBOCOR (magnetic levitation) compressors and flooded shell and tube exchangers for dry-cooler operation

_icona_clint_solo_raffreddamento_2024.png _icona_clint_compressore_turbocor_2024.png _icona_clint_exchanger_shell_and_tube_FL_2024.png _icona_clint_solution_web_monitoring_2024.png _icona_clint_solution_A_class_cooling_2024.png _icona_clint_refrigerant_HFO_2024.png

The innovative TWH/DR 341÷2061 TT/H units for Dry-Cooler operation, featuring A CLASS energy efficiency and HFO-R1234ze refrigerant, are designed to provide an effective solution to highly selective system needs. The latest generation refrigerant HFO-R1234ze, with GWP<1 (Global warming Potential), is the most environmentally sustainable refrigerant on the market, and meets the strictest international environmental regulations. Furthermore, thanks to Turbocor compressors, the units perform with top efficiency at partial loads, low inrush currents, an excellent silent functioning and reduced weight.
Using TURBOCOR dynamic partial-load oil-free magnetic levitation compressors, managed by the TURBOSOFT self-adaptive electronic control and flooded shell and tube evaporators, provide high energy performance, with unbeatable SEER values, with minimum water content, and an excellent silent functioning. Compared to traditional Screw compressor units, units have low operational costs during their entire use, with a savings that can even reach 50%.
The units are compliant to the 2021 ErP Regulation.

Versions

  • TWH/DR - Cooling only for Dry-Cooler

Power range

  • 301-1802 kW
  • 86.0-512 Ton

Features

  • Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
  • Semi-hermetic centrifugal compressors with dual Turbocor turbine, oil free, magnetic rising rotor, thermal protection, continuous capacity adjustment system thanks to built-in INVERTER, automatic anti-cavitation system. The power circuit of the compressor is fitted with a set of electrolytic condensers to control the rising in the event of a power failure, reactor for the power factor correction, EMI filter for electromagnetic compatibility.
  • Shell and tube type condenser, with easily removable cast iron heads to enable access for maintenance operations.
  • High efficiency flooded shell and tube type evaporator, with one circuit on the refrigerant side and one on the water side, complete with water differential pressure switch.
  • Cooling circuit shut-off valves on suction, discharge and liquid line.
  • Electronic expansion valve.
  • Electronic high and low pressure gauges.
  • HFO-R1234ze refrigerant.
  • Electrical board includes: main on-off switch with door lock, fuses, electronic/digital overload device to protect the compressors, interface relay and terminals for external connections.
  • TURBOSOFT control and regulation system, equipped with RS485 serial interface, can be supplied with an optional Web Monitoring device for remote monitoring via GPRS/EDGE/3G/TCP-IP network.

Factory fitted accessories

  • IM Automatic circuit breakers
  • HR Desuperheater
  • HRT Total heat recovery
  • FE Antifreeze heater for evaporator
  • TS Touch Screen Interface
  • WM Web Monitoring - Wireless remote monitoring (GPRS/EDGE/4G/TCP-IP)
  • IST Modbus TCP/IP protocol, Ethernet port
  • ISB BACnet MSTP protocol, RS485 serial interface
  • ISBT BACnet IP protocol, Ethernet port
  • ISS SNMP protocol, Ethernet port
  • IAV Remote set-point, 0-10V signal
  • IAA Remote set-point, 4-20mA signal
  • IAS Remote signal for second set-point activation
  • IDL Demand limit from digital input
  • CP Potential free contacts
  • IVV 0-10V signal for the management of the electronic pressostatic valve source side
  • MN High and low pressure gauges

Loose accessories

  • CR Remote control panel
  • AG Rubber shock absorbers
  • AM Spring shock absorbers
  • FL Flow switch
3416811031137117112061
CoolingCooling capacity (1)kW301603899120314991802
Absorbed power (1)kW71142212283354424
EER (1)4,244,254,244,254,234,25
Cooling (EN14511)Cooling capacity (1)kW300601896120014941797
Absorbed power (1)kW72144215286359429
EER (1)4,174,174,174,204,164,19
SEER (2)8,558,678,839,539,759,77
Energy Efficiency (2)%334339345373382383
CompressorQuantity123456
Refrigerant circuits111111
Capacity stepsSteplessSteplessSteplessSteplessSteplessStepless
EvaporatorWater flowl/s14,3828,8142,9557,4871,6286,10
Pressure dropskPa414241304744
Water connectionsDN100125150150200200
CondenserWater flowl/s19,438,858,077,796,7116
Pressure dropskPa555655566258
Water connectionsDN100125150150200200
Electrical characteristicsPower supplyV/Ph/Hz400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50
Max. running currentA150300450600750900
Max. starting currentA5155305455605755
Sound powerSTD version (3)dB(A)909395969798
Sound pressureSTD version (4)dB(A)727476767778
WeightsTransport weightkg1849291940656587794211716
Operating weightkg1990320045107340904013460

Dimensions

3416811031137117112061
LSTDmm340034003450455055006500
WSTDmm110011501800180018001800
HSTDmm180019502050210021002150

Notes

  • 1 Chilled water from 12 to 7 °C, temperature at the condenser (with ethylene glycol at 35%) from 40 to 45 °C.
  • 2 Seasonal energy efficiency of cooling at low temperature. According to EU Regulation n. 2016/2281.
  • 3 Sound power level according to Standard ISO 3744 and Eurovent 8/1.
  • 4 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.