JWV/WP 051÷182 S/P/P/HE

High efficiency super silenced air cooled dedicated Heat Pumps for high temperature hot water production (up to 70°C) with EC Inverter axial fans, Scroll compressors and plate exchanger

_icona_clint_solo_raffreddamento-riscaldamento_2024.png _icona_clint_compressore_scroll_2024.png _icona_clint_fan_assiale_inverter_2024.png _icona_clint_exchanger_plate_2024.png _icona_clint_solution_DHW_2024.png _icona_clint_solution_leaf-electric_2024.png _icona_clint_solution_A_class_heating_2024.png _icona_clint_refrigerant_R290_2024.png

ECO V-THERM is the new range of high temperature air-to-water reversible Heat Pumps designed to offer high performance while respecting the environment.
Equipped with Scroll compressors and EC axial fans with increased diameter, these units produce hot water up to 70 °C and operate with outdoor temperatures down to -20 °C, ensuring optimal comfort all year round with extremely quiet operation. They are ideal for environments with high daily occupancy, providing winter and summer air conditioning as well as high temperature domestic hot water production.
Using the natural refrigerant R290, with an extremely low GWP, they meet current and future European environmental regulations, combining efficiency and sustainability.


The units are designed for high temperature hot water production (up to 70°C).
The units are compliant to the ErP Regulation.

Versions

  • JWV/WP - Reversible Heat Pump

Power range

  • 52.0-166 kW
  • 15.0-47.0 Ton

Features

  • Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
  • Painted galvanised steel condensate pan complete with condensate drain (with siphon) and antifreeze electric heater.
  • Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
  • Axial fans with increased diameter directly coupled to three-phase Inverter external rotor motors. The EC Inverter fans allow the unit to run continuously and efficiently, ensuring low noise levels.
  • Condenser made of finned coils with copper tubes and aluminium fins with hydrophilic treatment positioned in a V-shaped geometry.
  • Evaporator AISI 316 stainless steel braze welded plates type with one (mod. 051÷091) or two (mod. 112÷182) independent circuits on the refrigerant side and one on the water side, completed with water differential pressure switch, and antifreeze heater.
  • R290 refrigerant.
  • The production of hot water up to 70 °C is reachable with outside air temperature down to 3 °C. With outside air temperature of -20 °C the reachable production of hot water is up to 55 °C.
  • Connection to the machine from a smartphone or tablet via local WiFi access point (IWF, included) or via IS-Modbus RTU protocol (IS, included).
  • Advanced functions: set point variation via digital control, 0-10V or 4-20 mA modulating input or via outside air temperature (climate curve); demand limit via digital control, 0-10V or 4-20 mA modulating input; Smart Grid Ready; hybrid system management; domestic hot water production management. User-enabled.
  • Electrical board includes: switch disconnector on power supply complete with safety door lock device, circuit breakers, thermal protection relays on compressors and thermo-contacts for fans.

Factory fitted accessories

  • RE Adjustable minimum/maximum voltage and phase control relay
  • PFC1 Power factor correction condensers (cosφ 0,95)
  • DSV Double relief safety valve with changeover switch on the high pressure side for each refrigerant circuit
  • BT Low water temperature kit
  • SI Inertial tank
  • PS Single circulating pump
  • PSI Inverter single circulating pump
  • PD Double circulating pump
  • PDI Inverter double circulating pump
  • GS Single circulating pump gasket for glycol >30%
  • GD Double circulating pump gaskets for glycol >30%
  • FO Antifreeze heater for tank and pipes
  • FG Antifreeze heater for single pump and pipes
  • FM Antifreeze heater for double pump and pipes
  • FUM Antifreeze heater for tank, single pump and pipes
  • FDM Antifreeze heater for tank, double pump and pipes
  • FEV Antifreeze heater for fans
  • SS Soft start
  • ISB1 BACnet MSTP protocol, RS485 serial interface, BTL certified.
  • ISBT1 BACnet IP protocol, Ethernet port, BTL certified.
  • IEH Gateway with Ethernet port. Possibility of connection via Modbus TCP-IP (IST) or SNMP (ISS) protocols or via Web Server
  • LDS Leak detection sensor R290
  • GP Anti-snow coils protection grids

Loose accessories

  • V3D 3-Way valve for domestic hot water production
  • AG Rubber shock absorbers
  • AM Spring shock absorbers
  • FL Flow switch
051071081091112132162182
HeatingHeating capacity (1)kW51,561,575,082,7103123150166
Absorbed power (1)kW13,816,419,722,327,833,039,845,0
COP (1)3,733,753,813,713,713,733,773,69
Heating capacity (2)kW52,863,077,485,1106126155171
Absorbed power (2)kW11,813,916,719,123,728,233,938,8
COP (2)4,494,524,624,454,454,474,564,41
Heating capacity (3)kW50,359,872,380,0101119144160
Absorbed power (3)kW16,219,022,825,632,738,346,351,8
COP (3)3,113,153,173,133,073,113,123,10
Heating (EN14511)Heating capacity (1)kW51,661,775,282,9103123150166
Absorbed power (1)kW14,016,720,122,728,033,240,245,5
COP (1)3,683,703,753,663,683,713,743,65
Heating capacity (2)kW52,963,177,685,3106126155171
Absorbed power (2)kW12,014,217,119,523,928,434,439,3
COP (2)4,424,444,534,374,424,444,514,36
Heating capacity (3)kW50,359,872,380,0101119145160
Absorbed power (3)kW16,219,122,925,732,838,446,451,9
COP (3)3,103,143,163,123,073,113,123,09
SCOP (4)3,894,0340,303,884,054,184,183,96
Energy Efficiency (4)%153158158152159164164155
Energy Class (5)A++A++A++-----
SCOP (6)3,473,523,523,413,613,663,653,49
Energy Efficiency (6)%136138138133141143143137
Energy Class (7)A++A++A++A++----
CoolingCooling capacity (8)kW40,748,260,468,080,896,6119133
Absorbed power (8)kW15,318,321,224,230,536,542,349,0
EER (8)2,662,632,852,812,652,652,812,71
Cooling capacity (9)kW55,164,782,191,7106126156173
Absorbed power (9)kW16,620,223,126,732,839,845,553,1
EER (9)3,333,213,553,443,253,173,433,25
Cooling (EN14511)Cooling capacity (8)kW40,648,160,367,980,796,5119133
Absorbed power (8)kW15,418,421,424,430,636,742,549,3
EER (8)2,632,612,822,782,642,632,802,69
Cooling capacity (9)kW55,064,581,891,4106126156172
Absorbed power (9)kW16,820,623,727,233,040,146,053,7
EER (9)3,273,143,463,373,223,133,393,21
SEER (10)3,493,423,713,623,773,703,963,48
Energy Efficiency (10)%137134145142148145155136
CompressorQuantity22224444
Refrigerant circuits11112222
Capacity steps22224444
EvaporatorWater flow (1)l/s2,502,963,634,004,975,947,258,02
Pressure drops (1)kPa35,635,740,737,214,014,522,226,6
Water connections"G2"2"2"2"2"1/22"1/22"1/22"1/2
Electrical characteristicsPower supplyV/Ph/Hz400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50
Max. running currentA414758698193115138
Max. starting currentA169172172222209218229291
Hydraulic circuit (Unit with pump)Pump available static pressure (1)kPa140135115115195185165150
Sound pressureSTD version (11)dB(A)5454575756565959
WeightsTransport weightkg8969259649731687175318501856
Operating weightkg9009309709801700177018701880

Dimensions

051071081091112132162182
LSTDmm24802480248024804990499049904990
WSTDmm13501350135013501350135013501350
HSTDmm22002200220022002200220022002200

Notes

  • 1 Heated water from 40 to 45 °C, ambient air temperature 7 °C d.b./6 °C w.b.
  • 2 Heated water from 30 to 35 °C, ambient air temperature 7 °C d.b./6 °C w.b.
  • 3 Heated water from 47 °C to 55 °C, ambient air temperature 7 °C d.b./6 °C w.b.
  • 4 Seasonal energy efficiency of heating at low temperature with average climatic conditions. According to EU Regulation n. 813/2013.
  • 5 Seasonal energy efficiency class of heating at low temperature with average climatic conditions. According to EU Regulation n. 811/2013.
  • 6 Seasonal energy efficiency of heating at medium temperature with average climatic conditions. According to EU Regulation n. 813/2013.
  • 7 Seasonal energy efficiency class of heating at medium temperature with average climatic conditions. According to EU Regulation n. 811/2013.
  • 8 Chilled water from 12 to 7 °C, ambient air temperature 35 °C.
  • 9 Chilled water from 23 to 18 °C, ambient air temperature 35 °C.
  • 10 Seasonal energy efficiency of cooling at low temperature. According to EU Regulation n. 2016/2281.
  • 11 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.