JWA/EP 051÷171.1 S/K/P

Aircooled 4-Pipe multifunctional units with axial fans, Scroll compressors and plate exchangers

_ktk_icon_versions_cooling_only.png _ktk_icon_versions_heting_only.png _ktk_icon_versions_cooling_heating.png _ktk_icon_compressor_scroll.png _ktk_icon_axial_fan.png _ktk_icon_plate.png _ktk_ICONA_4P.png _ktk_icon_DHW.png _ktk_icon_gsm.png _ktk_icon_refrigerant_R410A.png ktk_icon_refrigerant_R452B.png ktk_icon_refrigerant_R454B.png

ENERGYPOWER is the range of high efficiency multifunctional units for 4-Pipe systems.
The units JWA/EP 051÷171.1 S/K/P feature R410A refrigerant and Scroll compressors activated in series based on the requested thermal load, to reach high EER/COP/TER and SEER/SCOP energy values. Thanks to the advanced control system, the units can simultaneously fulfill the heating, cooling and domestic hot water request of the building. The unit can manage the opposed thermal loads at the same time and reach the highest possible efficiency. ENERGYPOWER units make the traditional layout of the technical plants easier because the production of thermal energy for the several users are joint in one unit only; the result is an advantage in terms of installation, maintenance and management and in the meantime of the comfort needs.
Are available as option the axial EC Inverter fans and the new EC Inverter fans with high available static pressure and efficiency for indoor ducted installation.
The units are designed for hot water production up to 55°C.
The units are compliant to the ErP Regulation.
On request, units can be supplied with R452B or R454B refrigerant.

Versions

  • JWA/EP - Multifunctional unit
  • JWA/EP/SSL - Super silenced multifunctional unit

Power range

  • 49.0-168 kW
  • 14.0-48.0 Ton

Features

  • Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
  • Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
  • Axial fans directly coupled to an electric motor with external rotor.
  • Copper tube and aluminum finned coil.
  • Condenser AISI 316 stainless steel braze welded plates type with one circuit on the refrigerant side and one on the water side, complete with water differential pressure switch. On the units it is always installed an antifreeze heater.
  • Evaporator AISI 316 stainless steel braze welded plates type with one circuit on the refrigerant side and one on the water side, complete with water differential pressure switch. On the units it is always installed an antifreeze heater.
  • Electronic expansion valve.
  • Electronic high and low pressure gauges.
  • R410A refrigerant. On request R452B or R454B refrigerant.
  • Electrical board includes: main switch with door safety interlock, fuses, thermal protection relays for compressors and thermocontacts for fans.
  • Condensing Control is included: electronic proportional device that ensures efficient and continuous functioning of the unit with outside air temperature down to –20 °C in cooling mode. It also allows to reduce the sound level especially at night. It consists of a fans speed controller with continuous speed regulation, high and low pressure transducers on cooling circuit and an electrical heater on electrical board.
  • Functioning in heating mode with outside air temperature down to -15 °C.
  • Microprocessor control and regulation system.

Factory fitted accessories

  • IM Automatic circuit breakers
  • PFC1 Power factor correction condensers (cosφ 0,95)
  • SL Unit silencement
  • RFM Cooling circuit shut-off valve on discharge line
  • RFL Cooling circuit shut-off valve on liquid line
  • BT Low water temperature kit
  • EC EC Inverter fans
  • ECH EC Inverter fans with high available static pressure
  • TX Coil with pre-coated fins
  • PSC Single circulating pump cooling side
  • PSIC Inverter single circulating pump cooling side
  • PDC Double circulating pump cooling side
  • PDIC Inverter double circulating pump cooling side
  • PSH Single circulating pump heating side
  • PSIH Inverter single circulating pump heating side
  • PDH Double circulating pump heating side
  • PDIH Inverter double circulating pump heating side
  • PSC+PSH Single circulating pump cooling side + heating side
  • PSIC+PSIH Inverter single circulating pump cooling side + heating side
  • PDC+PDH Double circulating pump cooling side + heating side
  • PDIC+PDIH Inverter double circulating pump cooling side + heating side
  • FNC Antifreeze heater for pipes cooling side
  • FGC Antifreeze heater for single pump and pipes cooling side
  • FMC Antifreeze heater for double pump and pipes cooling side
  • FNH Antifreeze heater for pipes heating side
  • FGH Antifreeze heater for single pump and pipes heating side
  • FMH Antifreeze heater for double pump and pipes heating side
  • SS Soft start
  • TS Touch Screen Interface
  • WM Web Monitoring - Wireless remote monitoring (GPRS/EDGE/3G/TCP-IP)
  • IS Modbus RTU protocol, RS485 serial interface
  • IST Modbus TCP/IP protocol, Ethernet port
  • ISB BACnet MSTP protocol, RS485 serial interface
  • ISBT BACnet IP protocol, Ethernet port
  • ISL LonWorks protocol, FTT-10 serial interface
  • ISS SNMP protocol, Ethernet port
  • IAA Remote set-point, 4-20 mA signal
  • IAS Remote signal for second set-point activation
  • IAV Remote set-point, 0-10 V signal
  • IDL Demand limit from digital input
  • CP Potential free contacts
  • GDS Leak detector

Loose accessories

  • MN High and low pressure gauges
  • CR Remote control panel
  • RP Coils protection metallic guards
  • AG Rubber shock absorbers
  • AM Spring shock absorbers
051061071081091101.1111.1121.1141171.1
Cooling onlyCooling capacity (1)kW48,655,963,272,281,895,1110122134168
Absorbed power (1)kW16,819,321,924,427,933,037,940,946,558,9
EER (1)2,892,902,892,962,932,882,902,982,882,85
Cooling only (EN14511)Cooling capacity (1)kW48,555,763,072,081,594,8110122134168
Absorbed power (1)kW17,019,622,324,828,432,938,441,647,259,8
EER (1)2,852,852,832,902,882,882,862,932,832,80
SEER (2)4,174,184,174,204,194,174,154,154,174,14
Energy Efficiency (2)%164164164165165164163163164163
Heating onlyHeating capacity (3)kW52,259,767,075,586,0105122134142184
Absorbed power (3)kW16,018,721,223,426,531,636,440,242,855,9
COP (3)3,263,193,163,233,253,323,353,333,323,29
Heating only (EN14511)Heating capacity (3)kW52,359,867,275,786,2105122134142184
Absorbed power (3)kW16,218,921,523,726,932,136,940,943,556,7
COP (3)3,233,163,133,193,213,283,313,293,273,25
SCOP (4)3,493,463,363,363,383,543,553,643,733,56
Energy Efficiency (4)%137135131131132139139143146139
Energy Class (5)A+A+A+A+------------
Cooling + HeatingCooling capacity (6)kW49,656,562,971,883,398,0112124140173
Heating capacity (6)kW64,973,982,594,1109127145161181224
Absorbed power (6)kW15,317,419,622,325,229,033,337,140,750,7
TER (6)7,487,497,427,447,637,767,737,687,897,82
Cooling + Heating (EN14511)Cooling capacity (6)kW49,556,362,771,683,097,6112124140173
Heating capacity (6)kW65,174,282,894,5109127146161181224
Absorbed power (6)kW15,918,120,523,426,430,434,738,842,753,0
TER (6)7,227,207,107,117,277,407,427,357,527,48
Evaporator - cooling sideWater flowl/s2,322,663,013,443,904,535,245,816,398,01
Pressure dropskPa35415350495643495058
Water connections"G2"1/22"1/22"1/22"1/22"1/22"1/22"1/22"1/22"1/23"
Condenser - heating sideWater flowl/s2,492,853,203,614,115,025,836,406,788,79
Pressure dropskPa31353842404041474850
Water connections"G2"1/22"1/22"1/22"1/22"1/22"1/22"1/22"1/22"1/23"
Electrical characteristicsPower supplyV/Ph/Hz400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50
Max. running currentA4046545966758593100120
Max. starting currentA164166178191234252261306314360
Unit with pump - cooling sidePump available static pressurekPa14913812011513011611494156130
Water connections"G2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"3"
Unit with pump - heating sidePump available static pressurekPa147135116112132106100153152120
Water connections"G2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"3"
ECH fan available static pressureSTD version Pa9510095959510060506050
SSL version Pa70857070709050506050
Sound pressureSTD version (7)dB(A)63646465656768686970
With SL accessory (7)dB(A)61626263636466666768
SSL version (7)dB(A)58595960606163636465
Weight STD versionsTransport weightkg75476381791193410271072130013081492
Operating weightkg76577583092595010451095132513351535

Dimensions

051061071081091101.1111.1121.1141171.1
LSTDmm2350235023502350235023502350355035503550
SSLmm2350235023502350235035503550355035504700
WSTD/SSLmm1100110011001100110011001100110011001100
HSTD/SSLmm1920192019202220222022202220222022202220

Notes

  • 1 Chilled water from 12 to 7 °C, ambient air temperature 35 °C.
  • 2 Seasonal energy efficiency of cooling at low temperature. According to EU Regulation n. 2016/2281.
  • 3 Heated water from 40 to 45 °C, ambient air temperature 7 °C d.b./6 °C w.b.
  • 4 Seasonal energy efficiency of heating at low temperature with average climatic conditions. According to EU Regulation n. 813/2013.
  • 5 Seasonal energy efficiency class of heating at low temperature with average climatic conditions. According to EU Regulation n. 811/2013.
  • 6 Chilled water from 12 to 7 °C, heated water from 40 to 45 °C.
  • 7 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
  • N.B. (1) Weights of SSL version are specified on technical brochure.