JCA 4÷40 S/K
Aircooled condensing units and reversible condensing units with axial fans and Rotary/Scroll compressor






The condensing units and reversible condensing units of the JCA 4÷40 S/K series, with R410A refrigerant, are designed for small and medium-sized domestic or industrial systems.
With a peraluman structure, these outdoor units are combined with evaporators in split system air conditioning installations, allowing the rooms to be cooled and dehumidified or to be heated. They can also be used in combination with hydronic evaporating units, generally in air conditioning applications
They are equipped with Rotary/Scroll compressors and axial fans, and they enable immediate and efficient use thanks to particular technical and design adjustments.
A wide range of accessories, factory fitted or supplied separately, complete the outstanding versatility and functionality of the series.
Versions
- JCA - Cooling only
- JCA/WP - Reversible Heat Pump
Power range
- 4.5-46.0 kW
- 1.3-13.0 Ton
Features
- Structure with supporting frame, in peraluman and galvanized sheet.
- Rotary/Scroll compressor with internal overheat protection and crankcase heater, if needed.
- Axial fans with low ventilation and special wing profile, directly coupled to external rotor motors.
- Condenser in copper tubes and aluminium finned coil complete with drain pan for WP version only (4÷20).
- R110A refrigerant.
- Electrical board includes: main switch with door lock device, fuses and compressor remote control switch.
- Microprocessor control and regulation system (WP only).
Accessories
Factory fitted accessories
- CC Condensing control down to -20 °C
- TX Coil with pre-coated fins
- VS Solenoid valve
Loose accessories
- CV Condensate drain pan (WP only)
- RP Coils protection metallic guards
- FP Coils protection metallic guards with filter
- AG Rubber shock absorbers
Technical data
4 | 5 | 7 | 8 | 9 | 11 | 14 | 16 | 18 | 20 | 24 | 27 | 34 | 40 | |||
Cooling | Cooling capacity (1) | kW | 4,5 | 5,6 | 6,8 | 8,0 | 9,2 | 10,8 | 13,2 | 15,8 | 19,1 | 21,2 | 26,4 | 30,9 | 36,6 | 45,9 |
Absorbed power (1) | kW | 1,4 | 1,8 | 2,1 | 2,5 | 2,9 | 3,7 | 4,1 | 5,1 | 6,2 | 7,1 | 8,6 | 9,2 | 11,5 | 14,2 | |
Heating | Heating capacity (2) | kW | 4,8 | 5,9 | 7,3 | 8,4 | 9,7 | 11,3 | 13,7 | 16,8 | 19,9 | 22,0 | 27,4 | 33,2 | 40,9 | 51,9 |
Absorbed power (2) | kW | 1,5 | 1,9 | 2,3 | 2,6 | 3,0 | 3,8 | 4,2 | 5,3 | 6,4 | 7,3 | 8,8 | 9,8 | 11,9 | 15,2 | |
Compressor | Quantity | n° | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
Type | Rotary | Rotary | Rotary | Rotary | Scroll | Scroll | Scroll | Scroll | Scroll | Scroll | Scroll | Scroll | Scroll | Scroll | ||
Connections | Suction line | Ø mm | 16 | 16 | 16 | 16 | 16 | 16 | 18 | 18 | 22 | 22 | 28 | 28 | 28 | 28 |
Liquid line | Ø mm | 10 | 10 | 10 | 10 | 10 | 10 | 12 | 12 | 12 | 12 | 12 | 12 | 12 | 16 | |
Electrical characteristics | Power supply | V/Ph/Hz | 230/1/50 | 230/1/50 | 230/1/50 | 230/1/50 | 230/1/50 | 230/1/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 |
Max. running current | A | 7 | 9 | 11 | 11 | 15 | 18 | 7 | 10 | 10 | 12 | 23 | 29 | 30 | 39 | |
Max. starting current | A | 37 | 43 | 62 | 62 | 79 | 86 | 58 | 61 | 58 | 74 | 142 | 147 | 142 | 167 | |
Sound pressure | (3) | dB(A) | 49 | 50 | 49 | 51 | 53 | 54 | 54 | 54 | 55 | 56 | 59 | 61 | 61 | 61 |
Weights | Transport weight | kg | 81 | 83 | 83 | 87 | 90 | 92 | 109 | 111 | 113 | 115 | 218 | 232 | 252 | 266 |
Operating weight | kg | 8 | 84 | 84 | 88 | 91 | 93 | 111 | 114 | 116 | 118 | 221 | 235 | 256 | 271 |
Dimensions
4 | 5 | 7 | 8 | 9 | 11 | 14 | 16 | 18 | 20 | 24 | 27 | 34 | 40 | |||
L | STD | mm | 870 | 870 | 870 | 870 | 870 | 870 | 1160 | 1160 | 1160 | 1160 | 1850 | 1850 | 1850 | 1850 |
W | STD | mm | 320 | 320 | 320 | 320 | 320 | 320 | 500 | 500 | 500 | 500 | 1000 | 1000 | 1000 | 1000 |
H | STD | mm | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1270 | 1270 | 1270 | 1270 | 1300 | 1300 | 1300 | 1300 |
Notes
- 1 Evaporating temperature 5 °C, ambient air temperature 35 °C.
- 2 Average condensing temperature 40 °C, ambient air temperature 7 °C d.b./6 °C w.b.
- 3 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
- N.B. (1) Weights of WP version are specified on technical brochure.
Documents
- Product overview (EN) _ktk_dpl_over_2022_ENG_w.pdf
- Product guides (EN) KTK_product_guide_ENG_2022_v08.pdf
- Technical brochures 24_jca_4À40-s-k_ktb_02.7.pdf
- Installation, use and maintenance manuals (IT) JCA_540_KTM_02_ab_GYN30lk.pdf
- Installation, use and maintenance manuals (EN) JCA_540_KTM_02_ab_f8fJi1c.pdf
- Installation, use and maintenance manuals (DE) JCA_540_SKM_02_cd_bOalEmO.pdf
- Installation, use and maintenance manuals (FR) JCA_540_SKM_02_cd_8B0m9tI.pdf