JCR 051÷172 S/K
Aircooled condensing units and reversible condensing units with radial fans and Scroll compressors






The indoor condensing units and reversible condensing units of the JCR 051÷172 S/K series, with R410A refrigerant, are designed to satisfy the needs of medium-sized domestic or industrial systems with particular difficulty in positioning units outside the building.
These units are combined with evaporators in split system air conditioning installations, allowing the rooms to be cooled and dehumidified or to be heated. They can also be used in combination with hydronic evaporating units in both air conditioning and industrial process cooling applications
They are equipped with Scroll compressors and radial fans even in a high ESP version, and they enable immediate and efficient use thanks to particular technical and design adjustments.
A wide range of accessories, factory fitted or supplied separately, complete the outstanding versatility and functionality of the series.
Versions
- JCR - Cooling only
- JCR/AP - Cooling only with high ESP fans
- JCR/WP - Reversible Heat Pump
- JCR/WP/AP - Reversible Heat Pump with high ESP fans
Power range
- 51.0-188 kW
- 14.0-54.0 Ton
Features
- Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
- Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
- Radial fans coupled to 3-phase motors by V belt and variable pulley.
- Condenser made of copper tubes and aluminium finned coil.
- R410A refrigerant.
- Electrical board includes: main switch with door safety interlock, fuses, thermal protection relays for compressors and thermocontacts for fans.
- Microprocessor control and regulation system.
Accessories
Factory fitted accessories
- IM Automatic circuit breakers
- SL Unit silencement
- RFM Cooling circuit shut-off valve on discharge line
- RFL Cooling circuit shut-off valve on liquid line
- CC Condensing control down to -20 °C
- TX Coil with pre-coated fins
- VS Solenoid valve
- BP Hot gas by-pass valve
- FF Dryer filter and sight glass
- SS Soft start
- IS Modbus RTU protocol, RS485 serial interface
- CP Potential free contacts
Loose accessories
- MN High and low pressure gauges
- CR Remote control panel
- RP Coils protection metallic guards
- FP Coils protection metallic guards with filter
- AG Rubber shock absorbers
- AM Spring shock absorbers
Technical data
051 | 061 | 071 | 081 | 091 | 101 | 111 | 131 | 152 | 172 | |||
Cooling | Cooling capacity (1) | kW | 50,6 | 58,6 | 66,9 | 77,2 | 88,4 | 102 | 117 | 134 | 156 | 188 |
Absorbed power (1) | kW | 18,3 | 21,4 | 24,9 | 28,2 | 31,9 | 36,6 | 43,2 | 49,6 | 58,2 | 69,2 | |
Heating | Heating capacity (2) | kW | 55,5 | 63,5 | 73,6 | 83,9 | 94,5 | 109 | 125 | 142 | 162 | 193 |
Absorbed power (2) | kW | 15,6 | 17,7 | 21,5 | 24,1 | 26,8 | 30,3 | 36,7 | 40,6 | 46,7 | 55,5 | |
Compressor | Quantity | n° | 2 | 2 | 2 | 2 | 2 | 3 | 3 | 3 | 4 | 4 |
Refrigerant circuits | n° | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 2 | 2 | |
Capacity steps | n° | 2 | 2 | 2 | 2 | 2 | 3 | 3 | 3 | 4 | 4 | |
Connections | Suction line | Ø mm | 1x35 | 1x35 | 1x35 | 1x35 | 1x35 | 1x42 | 1x42 | 1x42 | 2x35 | 2x35 |
Liquid line | Ø mm | 1x22 | 1x22 | 1x22 | 1x22 | 1x22 | 1x28 | 1x28 | 1x28 | 2x22 | 2x22 | |
Available static pressure | STD version | Pa | 165 | 147 | 120 | 120 | 105 | 115 | 135 | 135 | 190 | 105 |
High ESP version | Pa | 298 | 288 | 263 | 263 | 245 | 256 | --- | --- | 400 | --- | |
Electrical characteristics | Power supply | V/Ph/Hz | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 |
Max. running current | A | 43 | 48 | 57 | 61 | 70 | 80 | 94 | 107 | 122 | 146 | |
Max. starting current | A | 166 | 169 | 180 | 193 | 237 | 204 | 227 | 275 | 255 | 313 | |
Sound pressure | STD version (3) | dB(A) | 70 | 70 | 70 | 70 | 71 | 73 | 74 | 74 | 75 | 76 |
STD version with SL accessory (3) | dB(A) | 68 | 68 | 68 | 68 | 69 | 71 | 72 | 72 | 73 | 74 | |
High ESP version (3) | dB(A) | 71 | 71 | 71 | 71 | 72 | 74 | --- | --- | 76 | --- | |
High ESP version with SL accessory (3) | dB(A) | 69 | 69 | 69 | 69 | 70 | 72 | --- | --- | 74 | --- | |
Weights | Transport weight | kg | 595 | 600 | 670 | 680 | 725 | 825 | 865 | 895 | 1080 | 1185 |
Operating weight | kg | 605 | 610 | 680 | 690 | 735 | 840 | 880 | 910 | 1105 | 1215 |
Dimensions
051 | 061 | 071 | 081 | 091 | 101 | 111 | 131 | 152 | 172 | |||
L | STD/AP | mm | 2350 | 2350 | 2350 | 2350 | 2350 | 2350 | 2350 | 2350 | 3550 | 3550 |
W | STD/AP | mm | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 |
H | STD/AP | mm | 1705 | 1705 | 1705 | 1705 | 2005 | 2005 | 2005 | 2005 | 2005 | 2005 |
Notes
- 1 Evaporating temperature 5 °C, ambient air temperature 35 °C.
- 2 Average condensing temperature 40 °C, ambient air temperature 7 °C d.b./6 °C w.b.
- 3 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
- N.B. (1) Weights of WP versions are specified on technical brochure.
Documents
- Product overview (EN) _ktk_dpl_over_2022_ENG_w.pdf
- Product guides (EN) KTK_product_guide_ENG_2022_v08.pdf
- Technical brochures 27_jcr_051-172_s-k_ktb_35.7.pdf
- Installation, use and maintenance manuals (IT) JCR_051182_KTM35_ab_pwwNDvD.pdf
- Installation, use and maintenance manuals (EN) JCR_051182_KTM35_ab_YoqA4R4.pdf
- Installation, use and maintenance manuals (DE) JCR_051182_KTM_35_cd_I02PgIi.pdf
- Installation, use and maintenance manuals (FR) JCR_051182_KTM_35_cd_tZu87DM.pdf