JCR 4÷34 S/K
Aircooled condensing units and reversible condensing units with radial fans and Rotary/Scroll compressor for indoor ducted installation






The indoor condensing units and reversible condensing units of the JCR 4÷34 S/K series, with R410A refrigerant, are intended to satisfy the needs of small and medium-sized domestic or industrial systems with particular difficulty in positioning units outside the building.
With a prepainted plate structure, these units are combined with evaporators in split system air conditioning installations, allowing the rooms to be cooled and dehumidified or to be heated. They can also be used in combination with hydronic evaporating units, generally in air-conditioning applications.
They are equipped with Rotary/Scroll compressors and radial fans, with appreciable useful head, and they enable immediate and efficient use thanks to particular technical and design adjustments.
A wide range of accessories, factory fitted or supplied separately, complete the outstanding versatility and functionality of the series.
Versions
- JCR - Cooling only
- JCR/WP - Reversible Heat Pump
Power range
- 4.5-37.0 kW
- 1.3-10.0 Ton
Features
- Self-supporting prepainted steel frame.
- Rotary/Scroll compressor with internal overheat protection and crankcase heater, if needed.
- Double inlet radial fan statically and dynamically balanced directly driven by a electric motor (4÷20) or belt driven connected to a three-phase electric motor (24÷19).
- Condenser made of copper tubes and aluminium finned coil, complete with drain pan for WP version only.
- R110A refrigerant.
- Electrical board includes: main switch with door safety interlock, fuse and compressor remote control switch.
- Microprocessor control and regulation system (WP only).
Accessories
Factory fitted accessories
- CC Condensing control down to -20 °C
- TX Coil with pre-coated fins
- VS Solenoid valve
Loose accessories
- RP Coils protection metallic guards
- FP Coils protection metallic guards with filter
- AG Rubber shock absorbers
Technical data
4 | 5 | 7 | 8 | 9 | 11 | 14 | 16 | 18 | 20 | 24 | 27 | 34 | |||
Cooling | Cooling capacity (1) | kW | 4,5 | 5,6 | 6,8 | 8,0 | 9,2 | 10,8 | 13,2 | 15,8 | 19,1 | 21,2 | 26,4 | 30,9 | 36,6 |
Absorbed power (1) | kW | 1,5 | 1,9 | 2,2 | 2,6 | 3,0 | 3,8 | 4,9 | 5,9 | 7,0 | 7,9 | 10,3 | 10,4 | 13,5 | |
Heating | Heating capacity (2) | kW | 4,8 | 5,9 | 7,3 | 8,4 | 9,7 | 11,3 | 13,7 | 16,8 | 19,9 | 22,0 | 27,4 | 33,2 | 40,9 |
Absorbed power (2) | kW | 1,6 | 2,0 | 2,4 | 2,7 | 3,1 | 3,9 | 5,0 | 6,1 | 7,2 | 8,1 | 10,5 | 11,0 | 13,9 | |
Compressor | Quantity | n° | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
Type | Rotary | Rotary | Rotary | Rotary | Scroll | Scroll | Scroll | Scroll | Scroll | Scroll | Scroll | Scroll | Scroll | ||
Connections | Suction line | Ø mm | 16 | 16 | 16 | 16 | 16 | 16 | 18 | 18 | 22 | 22 | 28 | 28 | 28 |
Liquid line | Ø mm | 10 | 10 | 10 | 10 | 10 | 10 | 12 | 12 | 12 | 12 | 12 | 12 | 12 | |
Available static pressure | Pa | 90 | 90 | 80 | 80 | 80 | 80 | 115 | 115 | 115 | 115 | 150 | 150 | 160 | |
Electrical characteristics | Power supply | V/Ph/Hz | 230/1/50 | 230/1/50 | 230/1/50 | 230/1/50 | 230/1/50 | 230/1/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 |
Max. running current | A | 10 | 12 | 13 | 14 | 17 | 21 | 11 | 14 | 14 | 15 | 27 | 33 | 36 | |
Max. starting current | A | 40 | 46 | 65 | 65 | 82 | 89 | 61 | 64 | 61 | 77 | 146 | 151 | 148 | |
Sound pressure | (3) | dB(A) | 51 | 51 | 51 | 52 | 53 | 54 | 59 | 59 | 60 | 60 | 62 | 62 | 64 |
Weights | Transport weight | kg | 120 | 121 | 123 | 126 | 131 | 133 | 190 | 200 | 202 | 204 | 313 | 319 | 334 |
Operating weight | kg | 121 | 122 | 124 | 127 | 132 | 134 | 192 | 203 | 205 | 207 | 316 | 322 | 338 |
Dimensions
4 | 5 | 7 | 8 | 9 | 11 | 14 | 16 | 18 | 20 | 24 | 27 | 34 | |||
L | STD | mm | 900 | 900 | 900 | 900 | 900 | 900 | 900 | 900 | 900 | 900 | 1500 | 1500 | 1500 |
W | STD | mm | 550 | 550 | 550 | 550 | 550 | 550 | 690 | 690 | 690 | 690 | 800 | 800 | 800 |
H | STD | mm | 1425 | 1425 | 1425 | 1425 | 1425 | 1425 | 1725 | 1725 | 1725 | 1725 | 1425 | 1425 | 1425 |
Notes
- 1 Evaporating temperature 5 °C, ambient air temperature 35 °C.
- 2 Average condensing temperature 40 °C, ambient air temperature 7 °C d.b./6 °C w.b.
- 3 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
- N.B. (1) Weights of WP version are specified on technical brochure.