JWA 051÷172 S/K
Aircooled liquid Chillers and Heat Pumps with axial fans, Scroll compressors and shell and tube exchanger
The liquid Chillers and Heat Pumps of the JWA 051÷172 S/K series, with R410A refrigerant, are designed for medium-sized service sector or industrial ambients.
They are used, combined with Fan Coil units, for the air conditioning of the rooms or to remove the heat developed during industrial processes. They can be supplied with Modbus RTU protocol through RS485 serial interface.
Equipped with axial fans, Scroll compressors and shell and tube exchanger, even in the super silent version, these units can be completed by a hydraulic circuit with tank, with pump, with tank and pump or with AQUALOGIK technology.
The AQUALOGIK smart control system optimises the water set point and modulates the power supply voltage of the pump and the fans, thus making the use of the inertial tank superfluous. This obtains high energy efficiency, quiet operation and optimised dimensions and costs.
Are available as option the new EC Inverter fans with high available static pressure and efficiency for indoor ducted installation.
Units are compliant to the ErP 2021 Regulation for process cooling application; for comfort cooling application they are compliant if provided with EC or ECH accessory (EC Inverter fans).
On request, units can be supplied with R452B or R454B refrigerant.
Versions
- JWA - Cooling only
- JWA/WP - Reversible heat pump
- JWA/SSL - Super silenced cooling only
- JWA/WP/SSL - Super silenced reversible heat pump
- JWA/ST - Cooling only with AQUALOGIK technology
- JWA/WP/ST - Reversible heat pump with AQUALOGIK technology
- JWA/SSL/ST - Super silenced cooling only with AQUALOGIK technology
- JWA/WP/SSL/ST - Super silenced reversible Heat Pump with AQUALOGIK technology
Power range
- 49.0-188 kW
- 14.0-54.0 Ton
Features
- Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
- Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
- Axial fans directly coupled to an electric motor with external rotor.
- Condenser made of copper tubes and aluminium finned coil.
- Shell and tube type evaporator with one circuit on the refrigerant side and one on the water side in 051÷131 models; with two independent circuits on the refrigerant side and one on the water side in 152÷172 models, complete with water differential pressure switch.
- R410A refrigerant. On request R452B or R454B refrigerant.
- Electrical board includes: main switch with door safety interlock, fuses, thermal protection relays for compressors and thermocontacts for fans.
- On ST versions water circuit includes INVERTER circulating pump, safety valve and expansion vessel.
- On ST versions Condensing Control is included: electronic proportional device that ensures efficient and continuous functioning of the unit with outside air temperature down to –20 °C in cooling mode. It also allows to reduce the sound level especially at night. It consists of a fans speed controller with continuous speed regulation, an high/low pressure transducer on cooling circuit and an electrical heater on electrical board.
- Microprocessor control and regulation system (with AQUALOGIK technology on ST versions).
Accessories
Factory fitted accessories
- IM Automatic circuit breakers
- SL Unit silencement
- RFM Cooling circuit shut-off valve on discharge line
- RFL Cooling circuit shut-off valve on liquid line
- CT Condensing control down to 0 °C
- CC Condensing control down to -20 °C
- BT Low water temperature kit
- EC EC Inverter fans
- ECH EC Inverter fans with high available static pressure
- HR Desuperheater
- HRT/S Total heat recovery in series
- HRT/P Total heat recovery in parallel
- TX Coil with pre-coated fins
- EW External water connections
- SP Inertial tank
- PU Single circulating pump
- PUI Inverter single circulating pump
- PD Double circulating pump
- PDI Inverter double circulating pump
- SPU Inertial tank and single circulating pump
- SPUI Inertial tank and Inverter single circulating pump
- SPD Inertial tank and double circulating pump
- SPDI Inertial tank and Inverter double circulating pump
- GS Single circulating pump gasket for glycol >30%
- GD Double circulating pump gaskets for glycol >30%
- FE Antifreeze heater for evaporator
- FN Antifreeze heater for pipes
- FQ Antifreeze heater on evaporator/tank and pipes
- FZ Antifreeze heater for evaporator, single pump and pipes
- FH Antifreeze heater for evaporator, double pump and pipes
- FU Antifreeze heater for evaporator/tank, single pump and pipes
- FD Antifreeze heater for evaporator/tank, double pump and pipes
- SS Soft start
- IS Modbus RTU protocol, RS485 serial interface
- IAV Remote set-point, 0-10V signal
- IAA Remote set-point, 4-20mA signal
- IAS Remote signal for second set-point activation
- IDL Demand limit from digital input
- MN High and low pressure gauges
Loose accessories
- CR Remote control panel
- RP Coils protection metallic guards
- FP Coils protection metallic guards with filter
- AG Rubber shock absorbers
- AM Spring shock absorbers
- FL Flow switch
Technical data
051 | 061 | 071 | 081 | 091 | 101 | 111 | 131 | 152 | 172 | |||
Cooling | Cooling capacity (1) | kW | 49,0 | 55,0 | 62,4 | 73,3 | 84,3 | 95,2 | 109 | 129 | 149 | 179 |
Absorbed power (1) | kW | 16,6 | 18,8 | 21,5 | 25,3 | 28,6 | 31,6 | 37,5 | 43,7 | 50,7 | 58,8 | |
EER (1) | 2,95 | 2,93 | 2,90 | 2,90 | 2,95 | 3,01 | 2,91 | 2,95 | 2,94 | 3,04 | ||
Cooling (EN14511) | Cooling capacity (1) | kW | 48,9 | 54,9 | 62,2 | 73,0 | 84,1 | 95,0 | 109 | 129 | 149 | 179 |
Absorbed power (1) | kW | 16,7 | 19,0 | 21,9 | 25,8 | 29,0 | 32,0 | 38,0 | 44,2 | 51,4 | 59,5 | |
EER (1) | 2,92 | 2,89 | 2,85 | 2,84 | 2,90 | 2,97 | 2,86 | 2,91 | 2,89 | 3,00 | ||
Heating | Heating capacity (2) | kW | 55,7 | 61,9 | 70,2 | 80,7 | 91,4 | 105 | 119 | 137 | 156 | 188 |
Absorbed power (2) | kW | 17,8 | 19,6 | 22,8 | 25,7 | 29,1 | 33,4 | 38,1 | 44,2 | 51,1 | 61,0 | |
COP (2) | 3,13 | 3,16 | 3,08 | 3,14 | 3,14 | 3,14 | 3,12 | 3,10 | 3,05 | 3,08 | ||
Heating (EN14511) | Heating capacity (2) | kW | 55,8 | 62,1 | 70,5 | 81,1 | 91,7 | 105 | 119 | 137 | 156 | 188 |
Absorbed power (2) | kW | 18,0 | 19,9 | 23,4 | 26,4 | 29,7 | 34,0 | 38,9 | 44,9 | 52,0 | 61,9 | |
COP (2) | 3,10 | 3,12 | 3,02 | 3,07 | 3,09 | 3,10 | 3,07 | 3,06 | 3,01 | 3,04 | ||
Compressor | Quantity | n° | 2 | 2 | 2 | 2 | 2 | 3 | 3 | 3 | 4 | 4 |
Refrigerant circuits | n° | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 2 | 2 | |
Capacity steps | n° | 2 | 2 | 2 | 2 | 2 | 3 | 3 | 3 | 4 | 4 | |
Evaporator | Water flow | l/s | 2,34 | 2,62 | 2,98 | 3,49 | 4,02 | 4,54 | 5,19 | 6,15 | 7,10 | 8,53 |
Pressure drops | kPa | 22 | 29 | 50 | 55 | 40 | 39 | 45 | 36 | 43 | 38 | |
Water connections | "G | 1 ½" | 1 ½" | 2" | 2" | 2 ½" | 2 ½" | 2 ½" | 3" | 3" | 3" | |
Electrical characteristics | Power supply | V/Ph/Hz | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 |
Max. running current | A | 41 | 44 | 55 | 60 | 67 | 79 | 86 | 97 | 112 | 131 | |
Max. starting current | A | 164 | 166 | 179 | 192 | 235 | 202 | 218 | 264 | 244 | 298 | |
Electrical characteristics (ST versions) | Power supply | V/Ph/Hz | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 |
Max. running current | A | 44 | 48 | 59 | 63 | 71 | 84 | 90 | 102 | 116 | 135 | |
Max. starting current | A | 168 | 170 | 182 | 196 | 238 | 207 | 222 | 269 | 248 | 303 | |
Unit with tank and pump | Pump available static pressure | kPa | 160 | 150 | 125 | 110 | 140 | 185 | 170 | 170 | 155 | 145 |
Tank water volume | l | 470 | 470 | 470 | 470 | 470 | 470 | 470 | 470 | 660 | 660 | |
Water connections | "G | 2 ½" | 2 ½" | 2 ½" | 2 ½" | 2 ½" | 2 ½" | 2 ½" | 2 ½" | 2 ½" | 2 ½" | |
Unit ST versions | Water flow | l/s | 2,34 | 2,62 | 2,98 | 3,49 | 4,02 | 4,54 | 5,19 | 6,15 | 7,10 | 8,53 |
Pump available static pressure | kPa | 155 | 145 | 115 | 100 | 105 | 145 | 135 | 140 | 120 | 110 | |
Water connections | "G | 2 ½" | 2 ½" | 2 ½" | 2 ½" | 2 ½" | 2 ½" | 2 ½" | 2 ½" | 2 ½" | 2 ½" | |
ECH fan available static pressure | STD versions | Pa | 90 | 80 | 100 | 100 | 100 | 80 | 95 | 75 | 60 | 60 |
SSL versions | Pa | 85 | 85 | 75 | 75 | 70 | 50 | 70 | 60 | 60 | --- | |
ST versions | Pa | 90 | 80 | 100 | 100 | 100 | 80 | 95 | 75 | 60 | 60 | |
SSL/ST versions | Pa | 85 | 85 | 75 | 75 | 70 | 50 | 70 | 60 | 60 | --- | |
Sound pressure | STD and ST versions (3) | dB(A) | 61 | 61 | 64 | 64 | 65 | 67 | 67 | 67 | 67 | 67 |
With SL accessory (3) | dB(A) | 59 | 59 | 62 | 62 | 63 | 65 | 65 | 65 | 65 | 65 | |
SSL and SSL/ST versions (3) | dB(A) | 57,0 | 57,0 | 60,0 | 60,0 | 61,0 | 62,0 | 63,0 | 63,0 | 63,0 | --- | |
Weights | Transport weight (4) | kg | 641 | 661 | 701 | 719 | 844 | 931 | 971 | 1112 | 1192 | 1428 |
Operating weight (4) | kg | 660 | 680 | 720 | 740 | 870 | 960 | 1000 | 1150 | 1230 | 1470 | |
Weights (ST versions) | Transport weight | kg | 656 | 676 | 716 | 734 | 859 | 951 | 991 | 1132 | 1212 | 1448 |
Operating weight | kg | 675 | 695 | 735 | 755 | 885 | 980 | 1020 | 1170 | 1250 | 1490 |
Dimensions
051 | 061 | 071 | 081 | 091 | 101 | 111 | 131 | 152 | 172 | |||
L | STD-ST | mm | 2350 | 2350 | 2350 | 2350 | 2350 | 2350 | 2350 | 2350 | 3550 | 3550 |
SSL-SSL/ST | mm | 2350 | 2350 | 2350 | 2350 | 2350 | 2350 | 3550 | 3550 | 3550 | --- | |
W | STD-SSL-ST-SSL/ST | mm | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 |
H | STD-SSL-ST-SSL/ST | mm | 1950 | 1950 | 1950 | 1950 | 2250 | 2250 | 2250 | 2250 | 2250 | 2250 |
Notes
- 1 Chilled water from 12 to 7 °C, ambient air temperature 35 °C.
- 2 Heated water from 40 to 45 °C, ambient air temperature 7 °C d.b./6 °C w.b.
- 3 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
- 4 Unit without tank and pump.
- N.B. (1) Weights of SSL and WP versions are specified on technical brochure.
Documents
- Product overview (EN) _ktk_dpl_over_2022_ENG_w.pdf
- Product guides (EN) KTK_Product_Guide_ENG_05_2022.pdf
- Commercial leaflets (EN) _ktk_dpl_low_gwp_refrigerants_technical_handbook_ENG_07.2022.pdf
- Commercial leaflets (EN) _ktk_dpl_low_gwp_refrigerants_commercial_ENG_07.2022.pdf
- Technical brochures 10_jwa_051-172_s-k_ktb_31.7_1ynQDfo.pdf
- Installation, use and maintenance manuals (IT) IT_JWA_051_172_S_K__KTM-31.7_REV8.pdf
- Installation, use and maintenance manuals (IT) IT_JWA_051_172_S_G__KTM-31.8_REV6.pdf
- Installation, use and maintenance manuals (IT) IT_JWA_051_172_S_L__KTM-31.8_REV6.pdf
- Installation, use and maintenance manuals (EN) EN_JWA_051_172_S_K__KTM-31.7_REV8.pdf
- Installation, use and maintenance manuals (EN) EN_JWA_051_172_S_G__KTM-31.8_REV6.pdf
- Installation, use and maintenance manuals (EN) EN_JWA_051_172_S_L__KTM-31.8_REV6.pdf
- Installation, use and maintenance manuals (DE) DE_JWA_051_172_S_K__KTM-31.7_REV8.pdf
- Installation, use and maintenance manuals (DE) DE_JWA_051_172_S_G__KTM-31.8_REV6.pdf
- Installation, use and maintenance manuals (DE) DE_JWA_051_172_S_L__KTM-31.8_REV6.pdf
- Installation, use and maintenance manuals (FR) FR_JWA_051_172_S_K__KTM-31.7_REV8.pdf
- Installation, use and maintenance manuals (FR) FR_JWA_051_172_S_G__KTM-31.8_REV6.pdf
- Installation, use and maintenance manuals (FR) FR_JWA_051_172_S_L__KTM-31.8_REV6.pdf
- Installation, use and maintenance manuals (ES) ES_JWA_051_172_S_K__KTM-31.7_REV8.pdf
- Installation, use and maintenance manuals (ES) ES_JWA_051_172_S_G__KTM-31.8_REV6.pdf
- Installation, use and maintenance manuals (ES) ES_JWA_051_172_S_L__KTM-31.8_REV6.pdf