JWA 24÷40 S/IK/P/A

A CLASS energy efficiency aircooled liquid Chillers and Heat Pumps with axial fans, Inverter Scroll compressor and plate exchanger

_icona_clint_solo_raffreddamento_2024.png _icona_clint_solo_raffreddamento-riscaldamento_2024.png _icona_clint_compressore_scroll_inverter_2024.png _icona_clint_fan_assiale_2024.png _icona_clint_exchanger_plate_2024.png _icona_clint_exchanger_microchannel_coil_2024.png _icona_clint_solution_DHW_2024.png _icona_clint_solution_leaf-electric_2024.png _icona_clint_solution_A_class_cooling_2024.png _icona_clint_solution_A_class_heating_2024.png _icona_clint_refrigerant_R410A_2024.png _icona_clint_refrigerant_R452B_2024.png _icona_clint_refrigerant_R454B_2024.png

The liquid Chillers and Heat Pumps of the JWA 24÷40 S/IK/P/A series, with R410A refrigerant, are designed to satisfy the needs of small and medium domestic and service sector environments.
With a peraluman structure corrosion-resistant over time, these units can be combined with Fan Coil units or with intermediate heat exchangers for process cooling applications.
All units feature A CLASS energy efficiency and are equipped with Inverter control on Scroll compressor for a better efficiency at partial loads (SEER/IPLV/SCOP). The Microchannel condensing coil, available on the dedicated version, ensures an even higher efficiency (high EER), having a better heat exchange than traditional coils.
The units are compliant to the ErP Regulation.
On request, units can be supplied with R452B or R454B refrigerant.

Versions

  • JWA - Cooling only
  • JWA/MC - Cooling only with MICROCHANNEL coil
  • JWA/WP - Reversible heat pump

Power range

  • 26.0-48.0 kW
  • 7.3-14.0 Ton

Features

  • Structure with supporting frame, in peraluman and galvanized sheet. Sound-proofed compressor compartment.
  • DC INVERTER Scroll compressor with oil sight glass, internal overheat protection, crankcase heater and soundproofing cover.
  • Axial fans with low ventilation and special wing profile, directly coupled to external rotor motors.
  • Condenser made of copper tube and aluminum finned coils or aluminium MICROCHANNEL coils.
  • Evaporator AISI 316 stainless steel braze welded plates type, complete with water differential pressure switch. On the Heat Pump units it is always installed an antifreeze heater.
  • Electronic expansion valve.
  • R410A refrigerant. On request R452B or R454B refrigerant.
  • Electrical board includes: main switch with door safety interlock, fuses and pump remote control switch.
  • Condensing Control is included: electronic proportional device that ensures efficient and continuous functioning of the unit with outside air temperature down to -20 °C in cooling mode. It also allows to reduce the sound level especially at night. It consists of a fans speed controller with continuous speed regulation and high and low pressure transducers on cooling circuit.
  • Functioning in heating mode with outside air temperature down to -15 °C.
  • Microprocessor control and regulation system.
  • Advanced functions: remote set-point with 0-10V signal, remote set-point with 4-20mA signal, remote signal for second set-point activation, demand limit from digital input, management of hybrid systems, management of domestic hot water production.

Factory fitted accessories

  • BT Low water temperature kit
  • TX Coil with pre-coated fins
  • TXB Coil with epoxy treatment
  • PS Single circulating pump
  • GS Single circulating pump gasket for glycol >30%

Loose accessories

  • CR Remote control panel
  • IS Modbus RTU protocol, RS485 serial interface
  • RP Coils protection metallic guards
  • FP Coils protection metallic guards with filter
  • AG Rubber shock absorbers
24273440
Cooling STD versionsCooling capacity (1)kW25,830,535,942,3
Absorbed power (1)kW8,09,511,313,4
EER (1)3,223,213,183,16
Cooling STD versions (EN14511)Cooling capacity (1)kW25,730,435,842,2
Absorbed power (1)kW8,19,611,413,6
EER (1)3,193,163,133,11
SEER (2)4,424,164,214,22
Energy Efficiency (2)%174163165166
Cooling MC versionsCooling capacity (1)kW25,830,535,942,3
Absorbed power (1)kW7,99,411,213,3
EER (1)3,273,243,213,18
Cooling MC versions (EN14511)Cooling capacity (1)kW25,730,435,842,2
Absorbed power (1)kW8,09,511,313,5
EER (1)3,233,203,163,13
SEER (2)4,484,214,264,27
Energy Efficiency (2)%176165167168
Heating STD versionsHeating capacity (3)kW28,734,340,448,0
Absorbed power (3)kW8,19,911,814,0
COP (3)3,543,463,423,43
Heating STD versions (EN14511)Heating capacity (3)kW28,834,440,548,1
Absorbed power (3)kW8,210,112,014,2
COP (3)3,513,423,373,38
SCOP (4)3,743,753,543,74
Energy Efficiency (4)%147147139147
Energy Class (5)A+A+A+A+
SCOP (6)2,952,962,933,07
Energy Efficiency (6)%115115114120
Energy Class (7)A+A+A+A+
CompressorQuantity1111
EvaporatorWater flowl/s1,231,461,712,02
Pressure dropskPa20293131
Water connections"G1 ¼"1 ¼"1 ¼"1 ¼"
Electrical characteristicsPower supplyV/Ph/Hz400/3+N/50400/3+N/50400/3+N/50400/3+N/50
Max. running currentA21242734
Max. starting currentA11141518
Unit with pumpPump available static pressurekPa140115150105
Water connections"G1 ¼"1 ¼"1 ¼"1 ¼"
Sound pressureSTD versions (8)dB(A)60616262
MC versions (8)dB(A)59606161
WeightsTransport weightkg224239269283
Operating weightkg229244275289

Dimensions

24273440
LSTD/MCmm1850185018501850
WSTD/MCmm1000100010001000
HSTD/MCmm1300130013001300

Notes

  • 1 Chilled water from 12 to 7 °C, ambient air temperature 35 °C.
  • 2 Seasonal energy efficiency of cooling at low temperature. According to EU Regulation n. 2016/2281.
  • 3 Heated water from 40 to 45 °C, ambient air temperature 7 °C d.b./6 °C w.b.
  • 4 Seasonal energy efficiency of heating at low temperature with average climatic conditions. According to EU Regulation n. 813/2013.
  • 5 Seasonal energy efficiency class of heating at low temperature with average climatic conditions. According to EU Regulation n. 811/2013.
  • 6 Seasonal energy efficiency of heating at medium temperature with average climatic conditions. According to EU Regulation n. 813/2013.
  • 7 Seasonal energy efficiency class of heating at medium temperature with average climatic conditions. According to EU Regulation n. 811/2013.
  • 8 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
  • N.B. (1) Data of MC version are specified on technical brochure.
  • N.B. (2) Weights of WP version are specified on technical brochure.