JWA 24÷40 S/IK/P/A
A CLASS energy efficiency aircooled liquid Chillers and Heat Pumps with axial fans, Inverter Scroll compressor and plate exchanger
The liquid Chillers and Heat Pumps of the JWA 24÷40 S/IK/P/A series, with R410A refrigerant, are designed to satisfy the needs of small and medium domestic and service sector environments.
With a peraluman structure corrosion-resistant over time, these units can be combined with Fan Coil units or with intermediate heat exchangers for process cooling applications.
All units feature A CLASS energy efficiency and are equipped with Inverter control on Scroll compressor for a better efficiency at partial loads (SEER/IPLV/SCOP). The Microchannel condensing coil, available on the dedicated version, ensures an even higher efficiency (high EER), having a better heat exchange than traditional coils.
The units are compliant to the ErP Regulation.
On request, units can be supplied with R452B or R454B refrigerant.
Versions
- JWA - Cooling only
- JWA/MC - Cooling only with MICROCHANNEL coil
- JWA/WP - Reversible heat pump
Power range
- 26.0-48.0 kW
- 7.3-14.0 Ton
Features
- Structure with supporting frame, in peraluman and galvanized sheet. Sound-proofed compressor compartment.
- DC INVERTER Scroll compressor with oil sight glass, internal overheat protection, crankcase heater and soundproofing cover.
- Axial fans with low ventilation and special wing profile, directly coupled to external rotor motors.
- Condenser made of copper tube and aluminum finned coils or aluminium MICROCHANNEL coils.
- Evaporator AISI 316 stainless steel braze welded plates type, complete with water differential pressure switch. On the Heat Pump units it is always installed an antifreeze heater.
- Electronic expansion valve.
- R410A refrigerant. On request R452B or R454B refrigerant.
- Electrical board includes: main switch with door safety interlock, fuses and pump remote control switch.
- Condensing Control is included: electronic proportional device that ensures efficient and continuous functioning of the unit with outside air temperature down to -20 °C in cooling mode. It also allows to reduce the sound level especially at night. It consists of a fans speed controller with continuous speed regulation and high and low pressure transducers on cooling circuit.
- Functioning in heating mode with outside air temperature down to -15 °C.
- Microprocessor control and regulation system.
- Advanced functions: remote set-point with 0-10V signal, remote set-point with 4-20mA signal, remote signal for second set-point activation, demand limit from digital input, management of hybrid systems, management of domestic hot water production.
Accessories
Factory fitted accessories
- BT Low water temperature kit
- TX Coil with pre-coated fins
- TXB Coil with epoxy treatment
- PS Single circulating pump
- GS Single circulating pump gasket for glycol >30%
Loose accessories
- CR Remote control panel
- IS Modbus RTU protocol, RS485 serial interface
- RP Coils protection metallic guards
- FP Coils protection metallic guards with filter
- AG Rubber shock absorbers
Technical data
24 | 27 | 34 | 40 | |||
Cooling STD versions | Cooling capacity (1) | kW | 25,8 | 30,5 | 35,9 | 42,3 |
Absorbed power (1) | kW | 8,0 | 9,5 | 11,3 | 13,4 | |
EER (1) | 3,22 | 3,21 | 3,18 | 3,16 | ||
Cooling STD versions (EN14511) | Cooling capacity (1) | kW | 25,7 | 30,4 | 35,8 | 42,2 |
Absorbed power (1) | kW | 8,1 | 9,6 | 11,4 | 13,6 | |
EER (1) | 3,19 | 3,16 | 3,13 | 3,11 | ||
SEER (2) | 4,42 | 4,16 | 4,21 | 4,22 | ||
Energy Efficiency (2) | % | 174 | 163 | 165 | 166 | |
Cooling MC versions | Cooling capacity (1) | kW | 25,8 | 30,5 | 35,9 | 42,3 |
Absorbed power (1) | kW | 7,9 | 9,4 | 11,2 | 13,3 | |
EER (1) | 3,27 | 3,24 | 3,21 | 3,18 | ||
Cooling MC versions (EN14511) | Cooling capacity (1) | kW | 25,7 | 30,4 | 35,8 | 42,2 |
Absorbed power (1) | kW | 8,0 | 9,5 | 11,3 | 13,5 | |
EER (1) | 3,23 | 3,20 | 3,16 | 3,13 | ||
SEER (2) | 4,48 | 4,21 | 4,26 | 4,27 | ||
Energy Efficiency (2) | % | 176 | 165 | 167 | 168 | |
Heating STD versions | Heating capacity (3) | kW | 28,7 | 34,3 | 40,4 | 48,0 |
Absorbed power (3) | kW | 8,1 | 9,9 | 11,8 | 14,0 | |
COP (3) | 3,54 | 3,46 | 3,42 | 3,43 | ||
Heating STD versions (EN14511) | Heating capacity (3) | kW | 28,8 | 34,4 | 40,5 | 48,1 |
Absorbed power (3) | kW | 8,2 | 10,1 | 12,0 | 14,2 | |
COP (3) | 3,51 | 3,42 | 3,37 | 3,38 | ||
SCOP (4) | 3,74 | 3,75 | 3,54 | 3,74 | ||
Energy Efficiency (4) | % | 147 | 147 | 139 | 147 | |
Energy Class (5) | A+ | A+ | A+ | A+ | ||
SCOP (6) | 2,95 | 2,96 | 2,93 | 3,07 | ||
Energy Efficiency (6) | % | 115 | 115 | 114 | 120 | |
Energy Class (7) | A+ | A+ | A+ | A+ | ||
Compressor | Quantity | n° | 1 | 1 | 1 | 1 |
Evaporator | Water flow | l/s | 1,23 | 1,46 | 1,71 | 2,02 |
Pressure drops | kPa | 20 | 29 | 31 | 31 | |
Water connections | "G | 1 ¼" | 1 ¼" | 1 ¼" | 1 ¼" | |
Electrical characteristics | Power supply | V/Ph/Hz | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 |
Max. running current | A | 21 | 24 | 27 | 34 | |
Max. starting current | A | 11 | 14 | 15 | 18 | |
Unit with pump | Pump available static pressure | kPa | 140 | 115 | 150 | 105 |
Water connections | "G | 1 ¼" | 1 ¼" | 1 ¼" | 1 ¼" | |
Sound pressure | STD versions (8) | dB(A) | 60 | 61 | 62 | 62 |
MC versions (8) | dB(A) | 59 | 60 | 61 | 61 | |
Weights | Transport weight | kg | 224 | 239 | 269 | 283 |
Operating weight | kg | 229 | 244 | 275 | 289 |
Dimensions
24 | 27 | 34 | 40 | |||
L | STD/MC | mm | 1850 | 1850 | 1850 | 1850 |
W | STD/MC | mm | 1000 | 1000 | 1000 | 1000 |
H | STD/MC | mm | 1300 | 1300 | 1300 | 1300 |
Notes
- 1 Chilled water from 12 to 7 °C, ambient air temperature 35 °C.
- 2 Seasonal energy efficiency of cooling at low temperature. According to EU Regulation n. 2016/2281.
- 3 Heated water from 40 to 45 °C, ambient air temperature 7 °C d.b./6 °C w.b.
- 4 Seasonal energy efficiency of heating at low temperature with average climatic conditions. According to EU Regulation n. 813/2013.
- 5 Seasonal energy efficiency class of heating at low temperature with average climatic conditions. According to EU Regulation n. 811/2013.
- 6 Seasonal energy efficiency of heating at medium temperature with average climatic conditions. According to EU Regulation n. 813/2013.
- 7 Seasonal energy efficiency class of heating at medium temperature with average climatic conditions. According to EU Regulation n. 811/2013.
- 8 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
- N.B. (1) Data of MC version are specified on technical brochure.
- N.B. (2) Weights of WP version are specified on technical brochure.
Documents
- Product overview (EN) _ktk_dpl_over_2022_ENG_w.pdf
- Product guides (EN) KTK_Product_Guide_ENG_05_2022.pdf
- Commercial leaflets (EN) _ktk_dpl_low_gwp_refrigerants_technical_handbook_ENG_07.2022.pdf
- Commercial leaflets (EN) _ktk_dpl_low_gwp_refrigerants_commercial_ENG_07.2022.pdf
- Technical brochures 02_jwa_24-40_s-ik-p-a_ktb_191_5AF5FX0.pdf
- Installation, use and maintenance manuals (IT) IT_JWA_24_40_S_IK_P_A__KTM-191_REV4.pdf
- Installation, use and maintenance manuals (IT) IT_JWA_24_40_S_IG_P_A__KTM-191.1_REV0.pdf
- Installation, use and maintenance manuals (IT) IT_JWA_24_40_S_IL_P_A_REV0_20230707094017.pdf
- Installation, use and maintenance manuals (EN) EN_JWA_24_40_S_IK_P_A__KTM-191_REV4.pdf
- Installation, use and maintenance manuals (EN) EN_JWA_24_40_S_IG_P_A__KTM-191.1_REV0.pdf
- Installation, use and maintenance manuals (EN) EN_JWA_24_40_S_IL_P_A_REV0_20230707094017.pdf
- Installation, use and maintenance manuals (DE) DE_JWA_24_40_S_IK_P_A__KTM-191_REV4.pdf
- Installation, use and maintenance manuals (DE) DE_JWA_24_40_S_IG_P_A__KTM-191.1_REV0.pdf
- Installation, use and maintenance manuals (DE) DE_JWA_24_40_S_IL_P_A_REV0_20230707094018.pdf
- Installation, use and maintenance manuals (FR) FR_JWA_24_40_S_IK_P_A__KTM-191_REV4.pdf
- Installation, use and maintenance manuals (FR) FR_JWA_24_40_S_IG_P_A__KTM-191.1_REV0.pdf
- Installation, use and maintenance manuals (FR) FR_JWA_24_40_S_IL_P_A_REV0_20230707094023.pdf
- Installation, use and maintenance manuals (ES) ES_JWA_24_40_S_IK_P_A__KTM-191_REV4.pdf
- Installation, use and maintenance manuals (ES) ES_JWA_24_40_S_IG_P_A__KTM-191.1_REV0.pdf
- Installation, use and maintenance manuals (ES) ES_JWA_24_40_S_IL_P_A_REV0_20230707094023.pdf