JEE 051÷172 S/K/P

Condenserless liquid Chillers and Heat Pumps with Scroll compressors and plate exchanger

_icona_clint_solo_raffreddamento_2024.png _icona_clint_solo_raffreddamento-riscaldamento_2024.png _icona_clint_compressore_scroll_2024.png _icona_clint_exchanger_plate_2024.png _icona_clint_refrigerant_R410A_2024.png

JEE 051÷172 S/K/P series liquid Chillers and Heat Pumps for remote condensation, with R410A refrigerant, are designed to meet the needs of residential or industrial-type systems requiring high power together with space-saving and quiet operation. These units are ideal for indoor installation and, equipped with a self-contained structure, minimise overall dimensions while also facilitating installation and maintenance operations. Equipped with polyester plate powder painting structure, Scroll compressors and plate exchanger they have refrigerant and hydraulic circuits, even in the version with tank, with pump or tank and pump, complete with everything necessary for quick installation operations and for high energy efficiencies. A number of accessories, factory fitted or supplied separately, such as the desuperheater or the total heat recovery, enhance and complete the equipment of this range.

Versions

  • JEE - Cooling only
  • JEE/WP - Reversible Heat Pump

Power range

  • 51.0-176 kW
  • 14.0-50.0 Ton

Features

  • Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
  • Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
  • Evaporator AISI 316 stainless steel braze welded plates type with one circuit on the refrigerant side and one on the water side in 051÷131 models; with two independent circuits on the refrigerant side and one on the water side in 152÷172 models, complete with water differential pressure switch.
  • R410A refrigerant.
  • Electrical board includes: main switch with door safety interlock, fuses, thermal protection relays for compressors, interface relay and terminals for external connections.
  • Microprocessor control and regulation system.

Factory fitted accessories

  • IM Automatic circuit breakers
  • SL Unit silencement
  • RFM Cooling circuit shut-off valve on discharge line
  • RFL Cooling circuit shut-off valve on liquid line
  • BT Low water temperature kit
  • DS Desuperheater
  • RT Total heat recovery
  • FE Antifreeze heater for evaporator
  • FO Antifreeze heater for tank and pipes
  • SS Soft start
  • IS Modbus RTU protocol, RS485 serial interface
  • MN High and low pressure gauges

Loose accessories

  • CR Remote control panel
  • SPU Inertial tank and single circulating pump
  • SPD Inertial tank and double circulating pump
  • AG Rubber shock absorbers
  • AG1 Rubber shock absorbers for SPU and SPD modules
  • AM Spring shock absorbers
  • AM1 Spring shock absorbers for SPU and SPD modules
051061071081091101111131152172
CoolingCooling capacity (1)kW50,857,164,373,687,198,8114134149176
Absorbed power (1)kW15,417,319,021,625,829,432,938,743,551,5
HeatingHeating capacity (2)kW59,565,874,384,796,5107122148157194
Absorbed power (2)kW18,020,022,324,727,832,837,241,150,856,5
CompressorQuantity2222233344
Refrigerant circuits1111111122
Capacity steps2222233344
EvaporatorWater flowl/s2,432,733,073,524,164,725,426,417,108,41
Pressure dropskPa47424142404844514140
Water connections"G1 ¼"1 ¼"1 ¼"1 ¼"2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"
ConnectionsDelivery lineØ mm28282828282828282 x 282 x 28
Liquid lineØ mm22222222222222222 x 222 x 22
Electrical characteristicsPower supplyV/Ph/Hz400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50
Max. running currentA333943496064739098120
Max. starting currentA128137139164204161189234213264
Unit with tank and pumpPump available static pressurekPa105110100135120130120110120100
Tank water volumel300300300300300300300300300300
Expansion vessell12121212121212121212
Water connections"G2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"
Sound pressureSTD version (3)dB(A)59596060626161636464
With SL accessory (3)dB(A)56565757595858606161
WeightsTransport weight (4)kg347357376386397562581595669708
Transport weight (5)kg567577596606617782811825899938
Operating weight (4)kg350360380390405570590605680720
Operating weight (5)kg87088090091092510901120113512101250

Dimensions

051061071081091101111131152172
LUNITmm1200120012001200120022852285228522852285
WUNITmm680680680680680680680680680680
UNIT + SPU/SPDmm680680680680680680680680680680
HUNITmm1520152015201520152015201520152015201520
UNIT + SPU/SPDmm1520152015201520152015201520152015201520

Notes

  • 1 Chilled water from 12 to 7 °C, condensing temperature 50 °C.
  • 2 Heated water from 40 to 45 °C, evaporating temperature 0 °C.
  • 3 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
  • 4 Unit without tank and pump.
  • 5 Unit with tank and pump.
  • N.B. (1) Weights of WP version are specified on technical brochure.