JEE 4÷40 S/K/P
Condenserless liquid Chillers and Heat Pumps with Rotary/Scroll compressor and plate exchanger
The liquid Chillers and Heat Pumps for remote condensation of the JEE 4÷40 S/K/P series, with R410A refrigerant, are designed for domestic or service sector systems which require medium power, space-saving units and quiet operation. Combined with remote condenser, these units are ideal for indoor installation and, equipped with a self-contained structure, they reduce the overall dimensions to a minimum while at the same time making installation and maintenance operations easier.
Equipped with prepainted plate structure, Rotary/Scroll compressor and plate exchanger, these units have cooling and hydraulic circuits designed for quick installation and high energy efficiency, even in the version with tank and pump.
A wide range of accessories, factory fitted or supplied separately, complete the outstanding versatility and functionality of the series.
Versions
- JEE - Cooling only
- JEE/SP - Cooling only with tank and pump
- JEE/WP - Reversible Heat Pump
- JEE/WP/SP - Reversible Heat Pump with tank and pump
Power range
- 4.0-42.0 kW
- 1.1-12.0 Ton
Features
- Self-supporting prepainted steel frame.
- Rotary/Scroll compressor with internal overheat protection and crankcase heater, if needed.
- Evaporator AISI 96 stainless steel braze welded plates type, complete with water differential pressure switch.
- R110A refrigerant.
- Electrical board includes: main switch with door lock device, fuses, compressor and pump remote control switch.
- Water circuit for SP version includes: insulated tank, circulating pump, safety valve, gauge and expansion vessel.
- Microprocessor control and regulation system.
Accessories
Factory fitted accessories
- BT Low water temperature kit
- PS Single circulating pump
- GS Single circulating pump gasket for glycol >30%
- FE Antifreeze heater for evaporator
- FA Antifreeze heater for tank
Loose accessories
- CR Remote control panel
- IS Modbus RTU protocol, RS485 serial interface
- AG Rubber shock absorbers
Technical data
4 | 5 | 7 | 8 | 9 | 11 | 14 | 16 | 18 | 20 | 24 | 27 | 34 | 40 | |||
Cooling | Cooling capacity (1) | kW | 4,0 | 5,1 | 6,2 | 7,3 | 8,5 | 10,1 | 12,1 | 14,5 | 17,0 | 20,0 | 24,1 | 28,8 | 33,9 | 41,5 |
Absorbed power (1) | kW | 1,4 | 1,8 | 2,1 | 3,0 | 3,3 | 3,7 | 3,3 | 5,2 | 6,0 | 7,1 | 7,8 | 9,3 | 10,9 | 13,3 | |
Heating | Heating capacity (2) | kW | 5,1 | 6,4 | 8,2 | 9,4 | 10,7 | 13,2 | 15,5 | 18,5 | 22,0 | 25,9 | 30,4 | 36,4 | 43,0 | 53,2 |
Absorbed power (2) | kW | 1,5 | 1,9 | 2,4 | 2,7 | 3,0 | 4,2 | 4,5 | 5,5 | 6,5 | 7,7 | 8,3 | 10,1 | 11,7 | 14,2 | |
Compressor | Type | Rotary | Rotary | Rotary | Rotary | Scroll | Scroll | Scroll | Scroll | Scroll | Scroll | Scroll | Scroll | Scroll | Scroll | |
Quantity | n° | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
Evaporator | Water flow | l/s | 0,19 | 0,24 | 0,30 | 0,35 | 0,41 | 0,48 | 0,58 | 0,69 | 0,81 | 0,96 | 1,15 | 1,38 | 1,62 | 1,98 |
Pressure drops | kPa | 15 | 15 | 20 | 18 | 20 | 25 | 35 | 28 | 35 | 39 | 40 | 45 | 40 | 40 | |
Water connections | "G | 1" | 1" | 1" | 1" | 1" | 1" | 1" | 1" | 1" | 1" | 1" | 1" | 1" | 1" | |
Connections | Delivery line | Ø mm | 12 | 12 | 12 | 12 | 12 | 12 | 16 | 16 | 16 | 16 | 22 | 22 | 22 | 22 |
Liquid line | Ø mm | 10 | 10 | 10 | 10 | 10 | 10 | 12 | 12 | 12 | 12 | 12 | 12 | 12 | 16 | |
Electrical characteristics | Power supply | V/Ph/Hz | 230/1/50 | 230/1/50 | 230/1/50 | 230/1/50 | 230/1/50 | 230/1/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 |
Max. running current | A | 8 | 10 | 13 | 14 | 16 | 22 | 9 | 11 | 14 | 15 | 18 | 20 | 23 | 29 | |
Max. starting current | A | 37 | 43 | 62 | 62 | 75 | 86 | 50 | 71 | 74 | 74 | 142 | 142 | 147 | 197 | |
Unit SP versions | Water flow | l/s | 0,19 | 0,24 | 0,30 | 0,35 | 0,41 | 0,48 | 0,58 | 0,69 | 0,81 | 0,96 | 1,15 | 1,38 | 1,62 | 1,98 |
Pump available static pressure | kPa | 50 | 45 | 75 | 70 | 70 | 60 | 180 | 170 | 140 | 110 | 215 | 130 | 155 | 235 | |
Tank water volume | l | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 100 | 100 | 100 | 100 | |
Water connections | "G | 1" | 1" | 1" | 1" | 1" | 1" | 1" | 1" | 1" | 1" | 1" | 1" | 1" | 1" | |
Sound pressure | STD/SP version (3) | dB(A) | 39 | 39 | 39 | 39 | 41 | 43 | 43 | 44 | 45 | 47 | 49 | 49 | 50 | 50 |
Weights | Transport weight (4) | kg | 74 | 75 | 77 | 81 | 84 | 87 | 86 | 89 | 91 | 93 | 183 | 189 | 195 | 206 |
Operating weight (4) | kg | 75 | 76 | 78 | 82 | 85 | 88 | 88 | 91 | 93 | 95 | 186 | 192 | 198 | 209 |
Dimensions
4 | 5 | 7 | 8 | 9 | 11 | 14 | 16 | 18 | 20 | 24 | 27 | 34 | 40 | |||
L | STD | mm | 550 | 550 | 550 | 550 | 550 | 550 | 550 | 550 | 550 | 550 | 550 | 550 | 550 | 550 |
SP | mm | 550 | 550 | 550 | 550 | 550 | 550 | 550 | 550 | 550 | 550 | 1100 | 1100 | 1100 | 1100 | |
W | STD/SP | mm | 550 | 550 | 550 | 550 | 550 | 550 | 550 | 550 | 550 | 550 | 550 | 550 | 550 | 550 |
H | STD/SP | mm | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 |
Notes
- 1 Chilled water from 12 to 7 °C, condensing temperature 50 °C.
- 2 Heated water from 40 to 45 °C, evaporating temperature 0 °C.
- 3 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
- 4 Unit without tank and pump.
- N.B. (1) Weights of WP versions are specified on technical brochure.
Documents
- Product overview (EN) _ktk_dpl_over_2022_ENG_w.pdf
- Product guides (EN) KTK_Product_Guide_ENG_05_2022.pdf
- Technical brochures 20_jee_440-s-k-p_ktb_07.7.pdf
- Installation, use and maintenance manuals (IT) JEE__KTM_36_ab_nOIuR1Q.pdf
- Installation, use and maintenance manuals (EN) JEE__KTM_36_ab_raaEOH0.pdf
- Installation, use and maintenance manuals (DE) JEE__KTM_36_cd_X7J1sFn.pdf
- Installation, use and maintenance manuals (FR) JEE__KTM_36_cd_Lo98Pxl.pdf