_clint_logo_air_maxi.png

URT/EC/MS 051÷212 S/IK

Double Skin packaged Roof Top units with Inverter Scroll compressors, EC Inverter Plug-Fans and Mixing Box

_ktk_icon_versions_cooling_only.png _ktk_icon_versions_cooling_heating.png _ktk_icon_compressor_Scroll_inverter.png _ktk_icon_EC_INVERTER_PLUG_FAN_2016.png _ktk_icon_double_skin.png _ktk_icon_MS.png _ktk_icon_refrigerant_R410A.png

The double skin packaged Roof Top units of this series are the ideal solution for air conditioning of wide surfaces such as shopping malls and restaurants, canteens or for industrial areas. Those units feature Inverter Scroll compressor with R410A refrigerant and EC Inverter Plug-Fans. The highest efficiency at partial loads is guaranteed by the Inverter Scroll technology on compressor since its power is varied proportionally to the requested thermal load. Furthermore, the EC Inverter Plug-Fans with high energy efficiency backward blades are managed by an electronic control adjusting fans' rotational speed to adapt the air flow to the system capacity.
Equipped with extruded aluminium alloy sections and 50mm-thick sandwich panelling, these units are available in Cooling only and Reversible Heat Pump version.
The flat or pocket filters help to keep the air quality at a suitable level in order to guarantee appropriate hygiene standards.
The MS units have an high level of modularity and adaptability to every plant-engineering need: these units feature, in addition to the basic sections, a MIXING BOX.
The units are compliant to the ErP Regulation.

Versions

  • URT/EC/MS - Cooling only with EC Inverter Plug-Fans and Mixing Box
  • URT/EC/WP/MS - Reversible Heat Pump with EC Inverter Plug-Fans and Mixing Box

Power range

  • 58.0-252 kW
  • 17.0-72.0 Ton

Features

  • Structure of base perimeter made of steel sheet elements galvanised. Frame made of extruded aluminium alloy profiles connected by 3 way joints. Assembling of the base to the frame is of dual support and grants the walking on the base panels installation without sticking out screws. 50mm thick sandwich panels made of prepainted steel sheet; water proofing granted by gaskets having shape memory for perfect seal up even after repeated removals. Section connection is effected by means of assembling conic stirrups and water proofing is granted by gaskets.
  • DC INVERTER Scroll and ON-OFF Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
  • Condenser and evaporator with copper tube and aluminium finned coil.
  • High efficiency delivery reverse blade EC INVERTER PLUG-FANS, with electronic speed control to easily adapt to the system characteristics.
  • Electronic expansion valve.
  • R410A refrigerant.
  • Electrical board includes: door interlocking isolator, fuses, thermal protection relays on compressors, thermocontacts for the fans of the condensing unit and contactors for the fan motors of the air handling unit.
  • Electronic proportional device to decrease the sound level, with a continuous regulation of the fan speed. This device also allows the cooling functioning of the unit by external temperature till -20°C.
  • Microprocessor for the automatic control of the unit.

Factory fitted accessories

  • IM Automatic circuit breakers
  • SL Unit silencement
  • RFM Cooling circuit shut-off valve on discharge line
  • RFL Cooling circuit shut-off valve on liquid line
  • ECA EC Inverter fans on condensing section
  • TXC Condensing coil with pre-coated fins
  • TXE Evaporating coil with pre-coated fins
  • FT/M6 Soft bag filters efficency M6
  • FT/M7 Soft bag filters efficency F7
  • FT/M8 Soft bag filters efficency F8
  • FT/R6 Rigid bag filters efficency M6
  • FT/R7 Rigid bag filters efficency F7
  • FT/R8 Rigid bag filters efficency F8
  • FT/E Electrostatic filter
  • AT Constant air flow regulation control
  • AT/P Constant available static pressure regulation control
  • AT/C Control adjustment of the air flow according to the load
  • WS2 Hot water coil with 3-Way valve
  • EHG Electrical heater with step regulation
  • SQ Air quality sensor
  • SSA Active sanitation systems for air and rooms
  • PF Differential pressure switch filters control
  • IS Modbus RTU protocol, RS485 serial interface
  • IST Modbus TCP/IP protocol, Ethernet port
  • ISB BACnet MSTP protocol, RS485 serial interface
  • ISBT BACnet IP protocol, Ethernet port
  • ISL LonWorks protocol, FTT-10 serial interface
  • ISS SNMP protocol, Ethernet port
  • IAV Remote set-point, 0-10 V signal
  • IAA Remote set-point, 4-20 mA signal
  • IAS Remote signal for second set-point activation
  • IDL Demand limit from digital input
  • CP Potential free contacts
  • RP Coils protection metallic guards

Loose accessories

  • MN High and low pressure gauges
  • CR Remote control panel
  • AG Rubber shock absorbers

Complementary sections

  • UM Section with preparation for Humidifier
  • UM/EN Section Humidifier with electrodes immersed
  • F/CD Condensation endothermic hot air generator with modulating gas burner
051061071081091101111131152172212
CoolingCooling capacity (1)kW57,965,877,687,498,6113129145168198252
Absorbed power (1)(2)kW19,421,824,626,230,837,840,443,354,661,585,1
Cooling (EN14511)SEER (3)4,574,614,784,814,694,534,524,664,424,294,31
Energy Efficiency (3)%180181188189185178178183174169169
HeatingHeating capacity (4)kW60,267,276,888,6101115133151173204262
Absorbed power (4)(2)kW16,817,920,222,825,232,234,040,045,750,470,5
Heating (EN14511)SCOP (5)3,463,513,623,603,573,403,443,523,563,553,47
Energy Efficiency (5)%135137142141140133135138139139136
Air treatment sectionAir flowm³/s2,673,304,054,054,845,496,326,328,209,7912,31
Available static pressurePa250250250250250250250250250250250
Fan11222222244
FilterTipoG4G4G4G4G4G4G4G4G4G4G4
Condensing sectionCompressor22222222444
Refrigerant circuits11111111222
Capacity stepsSteplessSteplessSteplessSteplessSteplessSteplessSteplessSteplessSteplessSteplessStepless
Hot water coilHeating capacity (6)kW85100125125150175200200250300350
Air pressure dropsPa3031313131303636353557
Water flow (6)l/s2,032,392,992,993,584,184,784,785,977,178,36
Water pressure dropskPa4547484849445151535745
Water connections"G1­"½1­"½1"­½1"­½1"­½2"2"2"2"2 ½"2 ½"
Fan22222244446
Electrical heaterPower supplyV/Ph/Hz400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50
Heating capacitykW1521272727414141414855
Max absorbed currentA2230393939595959596979
Steps22222444444
Electrical characteristicsPower supplyV/Ph/Hz400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50
Max. running currentA555668688086104104140160207
Max. starting currentA138139190190203253245245272327395
Sound pressureSTD version (7)dB(A)6869686970727474737373
With SL accessory (7)dB(A)6566656667697171707070
WeightsTransport weightkg10701135124513401360156019401990230025203465
Operating weightkg10551120122513201340154019201970228025003435
Weight EC/WP/MS versionsTransport weightkg11701245126514701490171021202180252027603785
Operating weightkg11551230124514501470169021002160250027403755

Dimensions

051061071081091101111131152172212
LSTDmm38803880404040404040450052205220522052207250
WSTDmm22002200220022002200220022002200220022002200
HSTDmm21002340234023402340234023402340234025102510

Notes

  • 1 Evaporator inlet air temperature 27 °C d.b./19 °C w.b.; ambient air temperature 35 °C.
  • 2 Excluded the power absorbed by fans of air treatment section.
  • 3 Seasonal energy efficiency of cooling. According to EU Regulation n. 2016/2281.
  • 4 Condenser inlet air temperature 20 °C, ambient air temperature 7 °C d.b./6 °C w.b.
  • 5 Seasonal energy efficiency of heating with average climatic conditions. According to EU Regulation n. 2016/2281.
  • 6 Inlet air temperature 20 °C, water temperature 70/60 °C.
  • 7 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
  • N.B. (1) Weights of WP version are specified on technical brochure.