logo_vuoto trasparente.eps

clint tec_ec_inverter_fans_2025.eps

EDX 10÷90

Single or double skin ductable Fan Coil units with 5-speed or EC Inverter centrifugal fans

_icona_clint_solo_raffreddamento_2024.psd _icona_clint_solo_raffreddamento-riscaldamento_2024.psd _icona_epivent_fan_centrifugo_2025.psd _icona_epivent_fan_centrifugo_EC_2025.psd epivent_icon_singolo_pannello.psd epivent_icon_doppio_pannello.psd _icona_epivent_refrigerant_H2O_2025.eps
  • Fan: Centrifugal, Centrifughi EC Inverter
  • Refrigerant: H₂O

The Ductable Fan Coil units, EDX 10÷90 are the ideal solution to meet the air treatment needs of systems including distribution through ducting or directly into the room and installation in false ceilings or in service rooms. Units are built with self-supporting panels ensuring the highest levels of energy efficiency and silence.
When part of a hydronic system equipped with a Liquid Chiller, the unit generates cool air with instantaneous reaction. While, during the winter, if combined with a thermal system, it provides warm air, making possible to meet home or business heating needs. A wide range of accessories are available to complete the series, units are available for 2-Pipe and 4-Pipe systems, in two versions, single or double skin panel with self-threading screws to ensure minimum installation time, and easy inspection and maintenance.
The units equipped with EC Inverter motor modulate the air flow, adapting the performances instant to instant to the actual needs of the room to be conditioned, assuring a total comfort with greater energy savings.

Versions

  • EDX - Single panel base unit
  • EDX/GP - Double-panel base unit
  • EDX/EC - Single panel unit with EC Inverter fans
  • EDX/GP/EC - Double panel unit with EC inverter fans

Features

  • Single panel units are made of extremely thick galvanized steel-sheet resistant to rust, corrosion and chemical agents, with internal thermal-acoustic insulation. Internal thermal-acoustic insulation. Self-supporting and removable panels provided with holes for ceiling/wall mounting directly through the main casing.
  • Double-panel units are provided with 20mm thick panels made of internal galvanized stell-sheet and external pre-painted steel white RAL 9002 colour with glass fiber insulation. Self-supporting and removable panels provided with holes for ceiling/wall mounting directly through the main casing.
  • Double inclination condensate drain pan optimised for condensate drainage, provided with natural drain pipe (on the same side of coil connections) with external thermal insulation.
  • Heat exchanger coil made of copper pipes and aluminium fins, water connections provided with anti-torsion system, manual air vent and water drain valves.
  • Fan section provided with centrifugal fans with double air inlet and last generation plastic blades, directly coupled to a 5-Speed electric motor, with 3 speeds connected in the standard configuration.
  • Fan section provided with centrifugal fans with double air inlet and last generation plastic blades, directly coupled to the EC Inverter electronic motor. Modulating regulation with 0-10Vdc signal with control panels provided as accessory or with independent regulation system.
  • Universal connecting terminal (mounted).
  • Standard water connections on right side based on air flow direction. Reversible on site.

Factory fitted accessories

  • RX Coil water connections on the right side
  • LX Coil water connections on the left side
  • WS Hot water coil for 4-Pipe system
  • EH1 Supplementary electrical heater
  • EH2 Supplementary electrical heater enhanced
  • AFL1 Flat simple air filter
  • AFL2 Air filtering section with flat filter
  • AFL3 Air filtering section with undulated filter
  • AFP1 Flat simple air filter for GP versions
  • AFP2 Air filtering section with flat filter for GP versions
  • AFP3 Air filtering section with undulated filter for GP versions
  • UCB1 Universal regulation card with Modbus RTU protocol and BACNET
  • SNA Air temperature sensor for UCB1
  • SNW2 Summer/winter water temperature probe for UCB1
  • SNW3 Minimum water temperature probe for UCB1

Loose accessories

  • C Auxiliary condensate drain pan
  • MP Condensate drain pump
  • PLM Panel with air delivery grille
  • PLR Panel with air intake grille
  • PPM Panel with air delivery grille for GP versions
  • PPR Panel with air intake grille for GP versions
  • P3LM Delivery plenum with circular connections
  • P3LA Intake plenum with circular connections
  • P3PM Delivery plenum with circular connections for GP versions
  • P3PA Intake plenum with circular connections for GP versions
  • P9LM 90-degree delivery plenum
  • P9LA 90-degree intake plenum
  • P9PM 90-degree delivery plenum for GP versions
  • P9PA 90-degree intake plenum for GP versions
  • SSM Air supply labyrinth noise level silencer section
  • SSR Air intake labyrinth noise level silencer section
  • SPM Labyrinth silencer section on the supply side for GP versions
  • SPR Labyrinth silencer section on the intake side for GP versions
  • MBL Manual damper with closing 0-33%-100-67%
  • MBLS Damper with on/off servo-motor
  • MBP Manual damper with closing 0-33%-100-67% for GP versions
  • MBPS Damper with on/off servo-motor for GP versions
  • V23 3-Way on/off valves for 2-Pipe system
  • V23M 3-Way modulating valves for 2-Pipe system
  • V22 2-Way on/off valves for 2-Pipe system
  • V22M 2-Way modulating valves for 2-pipe system
  • V43 3-Way on/off valves for 4-Pipe system
  • V43M 3-Way modulating valves for 4-Pipe system
  • V42 2-Way on/off valves for 4-Pipe system
  • V42M 2-Way modulating valves for 4-Pipe system
  • TRA Transformer 230V/24V
  • TA1 Wall mounted electronic ambient thermostat for AC versions
  • VR1 Wall mounted electronic speed control panel for AC versions
  • DR1 Wall mounted manual electronic control panel for AC versions
  • DR2 Wall mounted automatic electronic control panel for AC versions
  • DRH1 Wall mounted configurable electronic control panel for AC versions
  • DRH2 Wall mounted configurable electronic control panel for AC/EC versions
  • SRH1 Wall mounted Wi-Fi configurable electronic control panel
  • IRC Digital wall control panel for UCB1
  • TRC Digital Touch Screen Wall Control Panel for UCB1
  • MC4 Multicontrol connection card for AC version
  • SNW4 Water temperature probe
  • TMB3 Minimum hot water temperature thermostat 32°C
  • TMB4 Minimum hot water temperature thermostat 42°C
102030405060708090
CoolingTotal cooling capacity (1, 2)kW---------------------------
Sensible cooling capacity (1, 2)kW---------------------------
Water flow (1, 2)l/h---------------------------
Pressure drops (1, 2)kPa---------------------------
HeatingHeating capacity (3, 2)kW---------------------------
Water flow (3, 2)l/h---------------------------
Pressure drops (3, 2)kPa---------------------------
RowsQuantity334334334
Water connectionsIn / Out"G1/2"1/2"1/2"1/2"1/2"1/2"1/2"1/2"1/2"
Additional coilHeating capacity (4, 2)kW---------------------------
Water flow (4, 2)l/h---------------------------
Pressure drops (4, 2)kPa---------------------------
Rows11---11---11---
Water connections (In / Out)"G1/2"1/2"---1/2"1/2"---1/2"1/2"---
Air flowMaxm³/h111012101210218022302230366036553650
Medm³/h92510851070144518801855303533403260
Minm³/h67077076097012051190226027102660
Air flow (EC version)Maxm³/h116012101200200023002300366036553650
Minm³/h560550550885880870132513001300
Available static pressureMaxPa656160726661665556
MedPa505050505050505050
MinPa182728212320323231
Available static pressure (EC version)MaxPa8259441017464373331
MinPa293022413733323017
EH1 Electrical heaterPower supplyV/Ph/Hz230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60
Absorbed powerkW222222222
Max absorbed currentA8,78,78,78,78,78,78,78,78,7
EH2 Electrical heaterPower supplyV/Ph/Hz230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60
Absorbed powerkW444444444
Max absorbed currentA17,417,417,417,417,417,417,417,417,4
Electrical characteristicsPower supplyV/Ph/Hz230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60
Max absorbed powerW174178169318324285514524498
Electrical characteristics (EC version)Power supplyV/Ph/Hz230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60
Max absorbed powerW116116116246300300438438438
Sound pressure intake sideMax (5)dB(A)545453565655565655
Med (5)dB(A)505251535554535554
Min (5)dB(A)404645404847414948
Sound pressure supply sideMax (5)dB(A)545453535452535352
Med (5)dB(A)505251485150505251
Min (5)dB(A)394645344241374544
Sound pressure intake side (EC version)Max (5)dB(A)545453565756565655
Min (5)dB(A)393837383635353434
Sound pressure supply side (EC version)Max (5)dB(A)545453535453535352
Min (5)dB(A)393837363432323231
WeightsTransport weightkg434446606266788184
Operating weightkg373840525457687073
Weight (GP version)Transport weightkg606163828487105107110
Operating weightkg525355717376919396

Dimensions

102030405060708090
LSTDmm800800800120012001200160016001600
GPmm840840840124012401240164016401640
WSTDmm605605605605605605605605605
GPmm625625625625625625625625625
HSTDmm275275275275275275275275275
GPmm315315315315315315315315315

Notes

  • 1 Ambient air temperature 27 °C d.b./19 °C w.b., water temperature 7/12 °C.
  • 2 Performances also valid for EC version.
  • 3 Ambient air temperature 20 °C d.b., water temperature 45/40 °C.
  • 4 Ambient air temperature 20 °C d.b., water temperature 65/55 °C.
  • 5 Sound pressure level measured at 1 m from the unit with reverberation time 0,5 s.
  • N.B. (1) Maximum inlet water temperature 90 °C.
  • N.B. (2) Inhibited ethylene glycol can be added to the water.
  • N.B. (3) Maximum operating pressure 1500 kPa.