clint ENERGY_POWER.eps

TWA/EP 172÷542.1 S/K/P

High efficiency air cooled 4-Pipe multifunctional units with axial fans, Scroll compressors and plate exchangers

_icona_clint_solo_raffreddamento_2024.psd _icona_clint_solo_riscaldamento_2024.psd _icona_clint_solo_raffreddamento-riscaldamento_2024.psd _icona_clint_compressore_scroll_2024.psd _icona_clint_fan_assiale_2024.psd _icona_clint_exchanger_plate_2024.psd _icona_clint_solution_DHW_2024.psd _icona_clint_solution_4P_2024.psd _icona_clint_refrigerant_R410A_2024.psd _icona_clint_refrigerant_R452B_2024.psd _icona_clint_refrigerant_R454B_2024.psd
  • Application: Comfort
  • Source: Air
  • Product Type: Multifunctional
  • Refrigerant: R410A, R452B, R454B
  • Fan: Axial, EC axial
  • Compressor: Scroll
  • Heat Exchanger: Plate

ENERGYPOWER is the range of high efficiency multifunctional units for 4-Pipe systems.
The units TWA/EP 172÷542.1 S/K/P feature R410A refrigerant and Scroll compressors activated in series based on the requested thermal load, to reach high EER/COP/TER and SEER/SCOP energy values. The units are characterized by double cooling circuit. Thanks to the advanced control system, the units can simultaneously fulfill the heating, cooling and domestic hot water request of the building. The unit can manage the opposed thermal loads at the same time and reach the highest possible efficiency.
Are available as option the EC Inverter axial fans and the new EC Inverter fans with high available static pressure and efficiency.


The units are designed for medium temperature hot water production (up to 55°C).
The models 604-P÷1404-P are compliant to ErP Regulations. The models 1604-P÷2004-P are compliant to ErP 2021 Regulations for comfort cooling application if provided with EC or ECH accessory (EC Inverter fans).
On request, units can be supplied with R452B or R454B refrigerant.

Versions

  • TWA/EP - Multifunctional unit
  • TWA/EP/SSL - Super silenced multifunctional unit

Power range

  • 152-502 kW
  • 43.0-143 Ton

Features

  • Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
  • Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
  • Axial fans directly coupled to an electric motor with external rotor.
  • Copper tube and aluminum finned coils with hydrophilic treatment.
  • Condenser AISI 316 stainless steel braze welded plates type with two independent circuits on the refrigerant side and one on the water side, complete with water differential pressure switch. On the units it is always installed an antifreeze heater.
  • Evaporator AISI 316 stainless steel braze welded plates type with two independent circuits on the refrigerant side and one on the water side, complete with water differential pressure switch. On the units it is always installed an antifreeze heater.
  • R410A refrigerant. On request R452B or R454B refrigerant.
  • Electrical board includes: main switch with door safety interlock, fuses, thermal protection relays for compressors and thermocontacts for fans.
  • Condensing Control is included: electronic proportional device that ensures efficient and continuous functioning of the unit with outside air temperature down to –20 °C in cooling mode. It also allows to reduce the sound level especially at night. It consists of a fans speed controller with continuous speed regulation, high and low pressure transducers on cooling circuit and an electrical heater on electrical board.
  • Functioning in heating mode with outside air temperature down to -15 °C.
  • Microprocessor control and regulation system.

Factory fitted accessories

  • IM Automatic circuit breakers
  • RE Adjustable minimum/maximum voltage and phase control relay
  • SL Unit silencement
  • RFM Cooling circuit shut-off valve on discharge line
  • RFL Cooling circuit shut-off valve on liquid line
  • BT Low water temperature kit
  • EC EC Inverter fans
  • ECH EC Inverter fans with high available static pressure
  • PSC Single circulating pump cooling side
  • PSIC Inverter single circulating pump cooling side
  • PDC Double circulating pump cooling side
  • PDIC Inverter double circulating pump cooling side
  • PSH Single circulating pump heating side
  • PSIH Inverter single circulating pump heating side
  • PDH Double circulating pump heating side
  • PDIH Inverter double circulating pump heating side
  • PSC+PSH Single circulating pump cooling side + heating side
  • PSIC+PSIH Inverter single circulating pump cooling side + heating side
  • PDC+PDH Double circulating pump cooling side + heating side
  • PDIC+PDIH Inverter double circulating pump cooling side + heating side
  • GS Single circulating pump gasket for glycol >30%
  • GD Double circulating pump gaskets for glycol >30%
  • GH Single circulating pump cooling side + heating side gaskets for glycol > 30%
  • GY Double circulating pump cooling side + heating side gaskets for glycol > 30%
  • FNC Antifreeze heater for pipes cooling side
  • FGC Antifreeze heater for single pump and pipes cooling side
  • FMC Antifreeze heater for double pump and pipes cooling side
  • FNH Antifreeze heater for pipes heating side
  • FGH Antifreeze heater for single pump and pipes heating side
  • FMH Antifreeze heater for double pump and pipes heating side
  • SS Soft start
  • TS Touch Screen Interface
  • WM Web Monitoring - Wireless remote monitoring (4G)
  • IS Modbus RTU protocol, RS485 serial interface
  • IST Modbus TCP/IP protocol, Ethernet port
  • ISBT BACnet IP protocol, Ethernet port
  • ISB1 BACnet MSTP protocol, RS485 serial interface, BTL certified
  • ISBT1 BACnet IP protocol, Ethernet port, BTL certified
  • ISS SNMP protocol, Ethernet port
  • IAA Remote set-point, 4-20mA signal
  • IAS Remote signal for second set-point activation
  • IAV Remote set-point, 0-10V signal
  • IDL Demand limit from digital input
  • CP Potential free contacts
  • GDS Leak detector
  • MN High and low pressure gauges

Loose accessories

  • CR Remote control panel
  • RP Coils protection metallic guards
  • AG Rubber shock absorbers
  • AG5 Rubber shock absorbers unit with pump on cooling or heating side only
  • AG6 Rubber shock absorbers unit with pump both on cooling and heating side
  • AM Spring shock absorbers
  • AM5 Spring shock absorbers unit with pump on cooling or heating side only
  • AM6 Spring shock absorbers unit with pump both on cooling and heating side
172212222242272302342.1392.1402.1492.1542.1
Cooling onlyCooling capacity (1)kW152175194219237271304347392463502
Absorbed power (1)kW54,966,775,084,394,4102114133144171184
EER (1)2,772,632,592,602,512,672,662,612,732,712,73
Cooling only (EN14511)Cooling capacity (1)kW152175194219237271304347392463502
EER (1)2,742,602,562,572,492,652,642,592,712,692,70
SEER (2)4,144,224,184,174,224,194,164,194,264,394,42
Energy Efficiency (2)%163166164164166165163165167173174
Heating onlyHeating capacity (3)kW178202229255279315363414463491562
Absorbed power (3)kW54,562,471,777,585,897,5113126140150172
COP (3)3,273,243,203,293,253,233,203,293,303,283,28
Heating only (EN14511)Heating capacity (3)kW178202229255279315363414464491563
COP (3)3,243,223,173,263,233,213,183,263,263,253,24
SCOP (4)3,373,363,653,583,433,633,393,263,433,453,49
Energy Efficiency (5)%132131143140134142133127134135137
Cooling + HeatingCooling capacity (5)kW156185208235256286320365406496538
Heating capacity (5)kW204242274306336378425478534636695
Absorbed power (5)kW48,056,565,971,580,292,4105113128140157
TER (5)7,497,557,327,577,387,187,097,447,348,067,85
Cooling + Heating (EN14511)Cooling capacity (5)kW156185208235256286320365406496538
Heating capacity (5)kW204242274306336378425478534636695
TER (5)7,497,557,327,577,387,187,097,447,348,067,85
CompressorQuantityn°44444444444
Refrigerant circuitsn°22222222222
Capacity stepsn°44444444444
Evaporator - cooling sideWater flowl/s7,248,349,2510,4411,2912,9214,4916,5418,6822,0723,93
Pressure dropskPa2523282319252930353238
Water connectionsDN100100100100100100100100125125150
Condenser - heating sideWater flowl/s8,619,7811,0812,3413,5015,2417,5620,0322,4023,7627,19
Pressure dropskPa2221253023283440483545
Water connectionsDN100100100100100100100100125125150
Electrical characteristicsPower supplyV/Ph/Hz400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50
Max. running currentA135154173189204227258300334372418
Max. starting currentA302342361402417463493613647704751
STD version with SL accessoryFann°444444688810
Air flowm³/s22,722,921,921,921,924,233,345,743,743,854,5
Unit with pump - cooling sidePump nominal powerkW3,03,03,03,03,04,04,05,55,55,57,5
Pump available static pressurekPa190185175165160150140185165140175
Expansion vessell1818181818181818181818
Water connectionsDN100100100100100100100100125125150
Unit with pump - heating sidePump nominal powerkW3,03,03,03,03,04,04,05,55,55,57,5
Pump available static pressurekPa180170160145135140120160135125160
Expansion vessell1818181818181818181818
Water connectionsDN100100100100100100100100125125150
Sound pressureSTD version (6)dB(A)6970707171727473747576
With SL accessory (6)dB(A)6667686868697171717273
SSL version (6)dB(A)6364656464666667676970
Weight STD versionsTransport weightkg22602285240524452475324534804410459046155290
Operating weightkg23002330245025002530331035454490467047255400

Dimensions

172212222242272302342.1392.1402.1492.1542.1
LSTDmm33503350335033503350500050006200620062007200
SSLmm33503350335050005000500062006200720072007200
WSTDmm22002200220022002200220022002200220022002200
SSLmm22002200220022002200220022002200220022002200
HSTDmm23602360236023602360236023602360236023602360
SSLmm23602360236023602360236023602360236023602360

Notes

  • 1 Acqua refrigerata da 12 a 7 °C. temperatura aria esterna 35 °C.
  • 2 Seasonal energy efficiency of cooling at low temperature. According to EU Regulation n. 2016/2281.
  • 3 Acqua riscaldata da 40 a 45 °C. temperatura aria esterna 7 °C b.s./6 °C b.u.
  • 4 Seasonal energy efficiency of heating at low temperature with average climatic conditions. According to EU Regulation n. 813/2013.
  • 5 Acqua refrigerata a 7 °C. alla portata d'acqua nominale; acqua riscaldata a 45 °C. alla portata d'acqua nominale.
  • 6 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
  • N.B. (1) Weights of SSL version are specified on technical brochure.